■[F 7] External input
This function available when external input function is equipped.
When the input signal is applied, accumulated value is reset at "0".
(Input signal: Connect input like to GND for 30 ms or longer)
External reset: When the input signal is applied, accumulated value is reset at "0".
Auto-shift: Function to perform output to relative change referring the instantaneous flow when signal is
input.
Auto-shift zero: Function to perform output to relative change and clear the display value as zero referring
the instantaneous flow when signal is input.
∗: PFM without external input function displays [---] and the function can not be set.
The flow and the set value on the negative side is relatively indicated by blinking the leftmost decimal point.
<Operation>
Press the
or
Select external input
[inP] and set value are displayed by turn.
Press the
or
Press the
[rA1] or [r01]: Only OUT1 is valid
[rA2] or [r02]: Only OUT2 is valid
[rAb] or [r0b]: Both OUT1, OUT2 are valid
button at function selection mode to display [F 7].
Press the
button.
button to select external input.
button to set.
Setting of [F 7] External input completed
Move on to select external input.
Return to function selection mode.
-34-