N N o o t t e e : : The chiller should remain within its protective
shrink-wrap covering during storage.
Trane Supplied
Type of Requirement
Trane Installed
Foundation
Rigging
•
Disassembly/Reassembly
(as required)
Isolation
•
•
Electrical
•
•
Water piping
Pressure Relief
•
Insulation
•
"Appendix B: Agility™
Chiller Installation
Completion and Request
for Trane Service," p. 70
(HDWA-ADF001*-EN;
refer to
"Appendix A:
Forms and Check
Sheets," p.
69)
•
Chiller start-up
commissioning
(a)
Post-commissioning
transport of empty
refrigerant containers for
return or recycling
(a)
Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products. Contractor shall
provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the
scheduled start-up.
HDWA-SVX001D-EN
Trane Supplied
Field Installed
Trane will perform or have
direct on-site supervision
of the disassembly and
reassembly work (contact
your local Trane office for
pricing)
•
•
Circuit breakers
Unit-mounted Adaptive
•
Frequency™ Drive (AFD)
Harmonic filter (optional)
•
Autotransformer
(optional)
•
•
Relief valves
Insulation (optional)
Trane, or an agent of
Trane specifically
authorized to perform
start-up of Trane®
products
Field Supplied
Field Installed
•
Meet foundation requirements
•
Safety chains
•
Rigging shackles
•
Lifting beam
•
Isolation pads
•
Optional spring isolators, when required, are
Isolation pads
installed by others; do NOT overload springs and do
NOT install isolation springs if they block serviceable
parts such as service valves, etc.
•
Electrical connections to unit-mounted AFD
•
Wiring sizes per submittal and National Electric Code
(NEC)
Temperature sensor
•
Ground connection(s)
(optional outdoor air)
•
BAS wiring (optional)
Flow switches (may be
•
Inter-processor communication (IPC) wiring
field supplied)
•
Control voltage wiring
Tracer® AdaptiView™
display and mounting
•
High condenser pressure interlock wiring
arm
•
Chilled water pump contactor and wiring
•
Condenser water pump contactor and wiring
•
Option relays and wiring
•
Thermometers
Flow switches (may be
field supplied)
•
Water flow pressure gauges
Condenser water
•
Isolation and balancing valves in water piping
regulating valve
•
Vents and drain valves
controller (optional;
may be field-supplied)
•
Pressure relief valves (for waterboxes as required)
•
Vent line and flexible connector
•
Insulation
•
To be completed by installing contractor prior to
contacting Trane for start-up
•
Move empty refrigerant containers to an easily
accessible point of loading
P P r r e e - - i i n n s s t t a a l l l l a a t t i i o o n n
17