Victaulic Gasket Installation; Screw-Tightening Sequence For Water; Piping Connections; Flanges With 8 Screws - Trane Agility HDWA Installation, Operation And Maintenance Manual

Water-cooled chillers with tracer adaptiview control
Table of Contents

Advertisement

The flange-adapter gasket must be placed with the
color-coded lip on the pipe and the other lip facing the
mating flange.
N N O O T T I I C C E E
P P i i p p i i n n g g C C o o n n n n e e c c t t i i o o n n L L e e a a k k s s ! !
F F a a i i l l u u r r e e t t o o p p r r o o v v i i d d e e e e f f f f e e c c t t i i v v e e s s e e a a l l c c o o u u l l d d r r e e s s u u l l t t i i n n
e e q q u u i i p p m m e e n n t t o o r r p p r r o o p p e e r r t t y y - - o o n n l l y y d d a a m m a a g g e e . .
T T o o p p r r o o v v i i d d e e e e f f f f e e c c t t i i v v e e s s e e a a l l , , g g a a s s k k e e t t c c o o n n t t a a c c t t s s u u r r f f a a c c e e s s
o o f f a a d d a a p p t t e e r r m m u u s s t t b b e e f f r r e e e e o o f f g g o o u u g g e e s s , , u u n n d d u u l l a a t t i i o o n n s s o o r r
d d e e f f o o r r m m i i t t i i e e s s . .

Victaulic Gasket Installation

1. Inspect supplied gasket to be certain it is suited for
intended service (code identifies gasket grade).
Apply a thin coat of silicone lubricant to gasket tips
and outside of gasket.
2. Install gasket, placing gasket over pipe end and
making sure gasket lip does not overhang pipe end.
Refer to the following figure for gasket
configuration.
3. Align and bring two pipe ends together and slide
gasket into position centered between the grooves
on each pipe. No portion of the gasket should
extend into the groove on either pipe.
Table 10. Installation data for 150 psig (1034.2 kPaG) flange adapters (Style 741)
Nominal Pipe Size
mm
in.
6
168.3
8
219.1
(a)
Screw size for conventional flange-to-flange connection. Longer screws are required when flange washer must be used. Grade 5 screws are
recommended.
Screw-Tightening Sequence for
Water Piping Connections
This section describes a screw-tightening sequence for
flanges with flat gaskets or O-rings. Remember that
improperly tightened flanges may leak.
N N o o t t e e : : Before tightening any of the screws, align the
flanges.

Flanges with 8 Screws

Tighten all screws to a snug tightness, following the
numerical sequence for the appropriate pattern as
shown in the following figure. Repeat this sequence to
apply the final torque to each screw.
HDWA-SVX001D-EN
Assembly
Number of Assembly
Screw Size
(a)
Screws Required
in.
3/4 x 3-1/2
8
3/4 x 3-1/2
8
I I n n s s t t a a l l l l a a t t i i o o n n : : W W a a t t e e r r P P i i p p i i n n g g
4. Open fully and place hinged Victaulic® flange
around the grooved pipe end with the circular key
section locating into the groove.
5. Insert a standard hex head screw through the
mating holes of the Victaulic® flange to secure the
flange firmly in the groove.
6. Tighten fasteners alternately and equally until
housing screw pads are firmly together (metal-to-
metal); refer to
"Screw-Tightening Sequence for
Water Piping Connections," p.
excessively tighten fasteners.
N N o o t t e e : : Uneven tightening may cause the gasket to
pinch.
Figure 20. Typical Victaulic® ® flange gasket
configuration
Screw Pattern Diameter
mm
in.
9.5
241
11.75
298
Figure 21. Flange screw tightening sequence (8
screws)
7
1
4
5
3
8
2
6
31. Do NOT
Weight
kg
lb
10.3
4.7
16.6
7.5
31