Configuration ProCommander LTC
6.4

Firmware update via batch-file

In the case that you have not installed the driver, follow
these steps:
Unzip all files of the ProComLTC_Vxxx.zip file, which
you can download from our website, in an empty
folder. xxx stands for the latest version of the software.
ProComLTC_V191.zip stands for the version 1.91.
Connect the ProCommander
USB-wire with the computer.
If you are asked to install a driver, then choose the \usb\
USBRS232driver\ folder, which you will find in your new
folder, where you have unzipped the attached files.
After the installation run the ProComLTC_UPD.BAT file.
62
You are asked for a COM
one, you have got after the above driver installation. If
you are not sure, open your device manager and look
for a AT32UC3 CDC USB to UART (COMx) connection. If
you have got a higher number than 8 for the x, change it
to a COM number between 1 and 8.
In the display of the ProCommander
see "UPDATE UNIT! PLEASE WAIT!"
LTC device through the
®
port
[1..8]. Please choose that
LTC you should
®