7.10 System Maintenance

7.10.1 Alarm Warning

Path 1:
Path 2: Main Menu
When there is a warning, the buzzer icon
sound. Tap the warning icon
After entering the WARNING screen (shown in the figure below), you can use the
page No. to check the warning logs. The system can store at maximum 200 warning logs.
The greater the event number is, the newer the event is.
The WARNING screen also displays relevant solutions. For warning solutions, please refer
to 10. Troubleshooting.
Ultron DPM series
Item
1
Dust Filter
1
1
1
1
means that the Administrator password is needed. For password information,
No.
No.
icons to view the warning logs or use the function key
Check the UPS's serial COM ID No.
if not, please select 'Disable'.
NOTE:
When the date is due, the yellow warning icon
will automatically appear in the upper right corner of
the LCD, and the alarm message ' DUST FILTER
REPLACEMENT ' will also appear.
Set up the Administrator password (4 digits).
will appear and the buzzer will make an alarm
to enter the WARNING screen.
7-40
Description
Enable';