Decommissioning; Standstill; Dismantling The Compressor; Disposing Of The Compressor - Bitzer ORBIT 6 Operating Instructions Manual

Hermetic scroll compressors
Table of Contents

Advertisement

Available languages

Available languages

NOTICE
!
!
Damage to the compressor caused by degraded
BVC oil.
Moisture is chemically bound to the oil and can-
not be removed by evacuation.
Proceed with extreme care:
Any penetration of air into the system and oil
drum must be avoided under all circumstances.
Use only oil drums in their original unopened
state!
Dispose of waste oil properly per local regulations!
ESB-130-8

9 Decommissioning

9.1 Standstill

Leave the oil heater (if available) switched on until dis-
assembly. This prevents increased refrigerant concen-
tration in the oil.
WARNING
Risk of refrigerant evaporation from the oil.
Increased risk of flammability, depending on the
refrigerant!
Shut-down compressors or used oil may still
contain rather high amounts of dissolved refri-
gerant.
Close the shut-off valves on the compressor
and extract the refrigerant!

9.2 Dismantling the compressor

WARNING
The compressor is under pressure!
Serious injuries are possible.
Depressurize the compressor!
Wear safety goggles!
Close the shut-off valves on the compressor. Extract
the refrigerant. In case of compressors without shut-off
valve, extract the entire refrigerant charge. Do not de-
flate the refrigerant, but dispose of it properly!

9.3 Disposing of the compressor

Drain the oil from the compressor. Dispose of waste oil
properly!
Dispose of the compressor properly per local regula-
tions!
39