Connection Options; Additional Components - Siemens SIMATIC TDC System Manual

Hardware
Hide thumbs Also See for SIMATIC TDC:
Table of Contents

Advertisement

Communication modules
6.6 CP52IO GDM interface module
6.6.5

Connection options

Figure 6-14
6.6.6

Additional components

Fiber-optic cable (FOC)
A fiber-optic cable with a core diameter of 62.5 μm/125 μm is used to interconnect the
CP52A0 GDM access module with the CP52IO GDM interface module. The cables are
connected using Duplex SC connectors.
The max. cable length for the connection between CP52IO and CP52A0 is 200 m.
The fiber-optic cables must be assembled in accordance with the plant topology and can be
ordered from the following supplier:
Ehret GmbH
Über der Elz 2
79312 Emmerdingen, Germany
138
Connection options of CP52IO
SIMATIC TDC hardware
System Manual, 12/2013, A5E01114865-07