Application Notes - Siemens SIMATIC TDC System Manual

Hardware
Hide thumbs Also See for SIMATIC TDC:
Table of Contents

Advertisement

7.5.2

Application notes

The interface module is equipped with a ribbon cable connector X1 that is used to connect
the output signals of the SIMATIC TDC system, as well as a terminal block X2 for wiring the
plant signals.
The interface module is designed only for vertical mounting positions due to thermal losses
to be dissipated.
Other information
For more information on EMC and environmental conditions, refer to section "General
technical specifications (Page 13)"!
Simultaneous operation of more than three digital outputs in short-circuit mode is not
allowed due to the maximum permissible thermal losses per interface cubicle.
The following figure shows a typical application:
Figure 7-11
SIMATIC TDC hardware
System Manual, 12/2013, A5E01114865-07
CAUTION
Application example of an SB71 interface module on digital I/O module SM500
Interface module
7.5 Interface module SB71
185