Green LED
The voltage supply (1P, 1M) on SIMATIC side is displayed by a green LED (P).
Red LED
The supply voltage on SIMATIC TDC side (1P, 1M) is short-circuited (fault).
7.2.1

Signals

Signals up to a maximum of 120 V (nominal value) DC or AC can be connected at the SB60
interface module.
Yellow LED
The status of the binary interface module outputs (binary inputs for SIMATIC TDC) is
indicated using yellow LEDs (1...8).
Terminal block X2 provides two screw terminals for each signal:
● terminals 12, 22, ... up to 82 for binary signals 120 V
● terminals 11, 21, ... up to 81 for the reference point
7.2.2

Application notes

The interface module is designed only for vertical mounting positions due to thermal losses
to be dissipated.
Other information
For more information on EMC and environmental conditions, refer to section "General
technical specifications (Page 13)"!
SIMATIC TDC hardware
System Manual, 12/2013, A5E01114865-07
Note
When wiring the signal lines to the terminals, observe "Installation and EMC Directives" in
the User Manual.
Interface module
7.2 Interface module SB60