Rack
2.1 Rack UR5213 (6DD1682-0CH2)
2.1.5

Power supply

Mains connection
Mains is connected to the 3-pin screw terminal block on the right side of the power supply
unit.
Note
Always use the integrated strain relief for the mains cable on the 3-pin screw terminal block.
The pin assignment is printed onto the front panel.
Input voltage
Test voltage
Primary ↔ PE
Power consumption
Conductor cross-section
External fuse
(dimensioning)
Note
A mains disconnect unit must be provided during installation of the rack.
42
85–264 V AC
1350 V AC
800 W (apparent power approx. 835 VA)
3x1.5 mm2 (stranded wires dressed with wire end ferrules with
ISO insulating collars)
In = 9 A
Is = <40 A (inrush peak)
The power supply is equipped with an internal 20 A fuse. This
means that only the mains supply has to be fused. It is
recommended to use a standard 16 A thermo magnetic circuit-
breaker (B characteristic).
Alternatively, a slow-acting fuse may be used.
SIMATIC TDC hardware
System Manual, 12/2013, A5E01114865-07