Heat & Glo SL-3X-IFT Installation Manual page 27

Hide thumbs Also See for SL-3X-IFT:
Table of Contents

Advertisement

Top Vent - Vertical Termination - (continued)
Three Elbows
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when
using flex vent except when
using the simple up and out
installation. See Figure 4.9.
Figure 4.17
Heat & Glo • SL-3X-IFT, SL-5X-IFT, SL-7X-IFT, SL-9X-IFT Installation Manual • 2472-980 Rev. Q • 3/20
1/2 ft..
1-1/2 ft.
2-1/2 ft.
3-1/2 ft.
4-1/2 ft.
V
2
H
2
INSTALLED
HORIZONTALLY
V
H
+ H
Maximum
1
1
2
90º Elbow
0
152 mm
1 ft.
457 mm
2 ft.
762 mm
4 ft.
1.1 m
6 ft.
1.4 m
14 ft.
H
Maximum = 14 ft. (4.3 m)
1
*No specific restrictions on this value EXCEPT V
CANNOT exceed 40 ft. (12.2 m).
H
1
ALL MODELS
V
2
0
1-1/2 ft. 457 mm 1-1/2 ft. 457 mm
305 mm
*
*
610 mm
*
*
1.2 m
*
*
1.8 m
*
*
4.3 m
*
*
+ V
1
V
1
V
+ V
Minimum
1
2
*
*
*
*
*
*
*
*
*
*
+ H
+ H
2
1
2
27