Top Vent - Horizontal Termination
One Elbow
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when
using flex vent except when
using the simple up and out
installation. See Figure 4.9.
WARNING *
Fire Risk.
• When using SLP-HRC-SS termination cap
on top vented fireplaces, a one foot minimum
vertical vent section is required before installing
first elbow.
Figure 4.11
22
Heat & Glo • SL-3X-IFT, SL-5X-IFT, SL-7X-IFT, SL-9X-IFT Installation Manual • 2472-980 Rev. Q • 3/20
V Minimum
90º Elbow*
1 ft.
1/2 ft.*
152 mm
2 ft.
1-1/2 ft.*
457 mm
3 ft.
2-1/2 ft.*
762 mm
5 ft.
3-1/2 ft.
1.1 m
7 ft.
4-1/2 ft.
1.4 m
15 ft.
H
Maximum= 15 ft. (4.6 m)
1
V
+ H
Maximum= 40 ft. (12.2 m)
1
1
* See warning below
H
1
H Maximum
All Models
305 mm
610 mm
914 mm
1-1/2 m
2.1 m
4.6 m
V
1