Top Vent - Vertical Termination - (continued)
Two 90º Elbows
Note: Use SLP Series
components only.
Figure 4.16
26
Heat & Glo • SL-3X-IFT, SL-5X-IFT, SL-7X-IFT, SL-9X-IFT Installation Manual • 2472-980 Rev. Q • 3/20
V
Minimum
1
90º Elbow
1/2 ft.
152 mm
1-1/2 ft.
457 mm
2-1/2 ft.
762 mm
3-1/2 ft.
1.1 m
4-1/2 ft.
1.4 m
V
1
*No specific restrictions on this value EXCEPT V
V
2
H
1
ALL MODELS
H
Maximum
1
1 ft.
305 mm
2 ft.
610 mm
3 ft.
914 mm
5 ft.
1.5 m
7 ft.
2.1 m
15 ft.
4.6 m
H
Maximum= 15 ft. (4.6 m)
1
+ V
+ H
Maximum = 40 ft. (12.2 m)
2
1
1
40 ft. (12.2 m)
Note: There MUST be a 25%
reduction in total H when
using flex vent except when
using the simple up and out
installation. See Figure 4.9.
V
1
V
V
+ V
Minimum
2
1
2
*
*
*
*
*
*
*
*
*
*
*
*
+ V
+ H
CANNOT exceed
2
1