Data backup

The current commissioning data can be saved, including the date and
the year. The data saved or the factory settings can be retrieved, if
required.
Main menu > Data backup > Storage date (read only):
Main menu > Data backup > Storage year (read only):
Main menu > Data backup > Restore:
Main menu > Data backup > Save:
Main menu > Data backup > Restore factory setting:
When saving the new data, any data previously saved in the
backup storage is overwritten (cannot be retrieved).
When restoring data or the factory settings, the current data
set in the device's main storage is overwritten (cannot be
retrieved).
When restoring data, certain bus settings and all texts set are
not overwritten and are therefore retained with their present
state. When restoring the factory settings, customized texts
are also reset.

System limits

System limitations (TP1 bus)
126
Central apartment units QAX910
Limitations per central apartment unit
1
Meteo sensor
12
Rooms
2
Door contacts (monitored)
4
Light actuators with status indication (only on KNX TP1(S-Mode))
3
RF repeaters
64
RF devices (total number, including the central apartment unit)
In addition to the above mentioned devices, switch, dim and
blind actuators can be used in unlimited numbers.
Limitations per room
1
Room unit
2
Room temperature sensor
1
Heating circuit controller
6
Radiator control actuators
(one lead controller, 0...5 lag controllers)
or heating circuit controller channels
6
Window contacts
1
Smoke detector
Radiator control actuators and heating circuit controllers can-
not simultaneously be used in the same room.
Siemens
Building Technologies
Synco 900
System limits
79/88