Heat demand relay
When the appropriately defined output terminal closes, a heat de-
mand signal is transmitted to the heat source.
State whether a heat demand relay is used and how it is controlled.
Setting
---
Via RF
Q1 (local)
Main menu > Commissioning > Basic configuration > Outputs >
Heat demand relay:
Factory setting
Your setting
Heat demand 0..10 V
The current heat demand can be transmitted to the heat source in the
form of a 0..10 V signal.
The temperature values corresponding to 0 V and 10 V and the
threshold value for a valid heat request can be set (refer to page 78).
State whether the 0..10 V heat demand output is used and how it is
controlled.
Setting
---
Via RF
Main menu > Commissioning > Basic configuration > Outputs >
Heat dem 0..10 V:
Factory setting
Your setting
32/88
Siemens
Building Technologies
Description
Inactive – heat demand relay not
required
Relay output Qx of an RRV91... heat-
ing circuit controller used as a heat de-
mand relay
Relay output Q1 of the central apart-
ment unit used as a heat demand relay
---
---
Via RF
Q1 (local)
Description
Inactive – 0..10 V heat demand output
not required
Universal output U of the RRV912...
heating circuit controller used as a
0..10 V heat demand output
---
---
Via RF
Synco 900
Commissioning the system
CE1C2707en
05.07.2007