Main menu > Commissioning > Basic configuration > Faults >
Fault input X:
Fault input
1
2
3
4
Fault outputs 1 and 2
If system faults occur, they can be forwarded to an external
component by closing a fault output.
You can select the fault priority and origin of fault for the relay to
close. For a description of these settings, refer to the Operating
Instructions, section "Faults".
State whether a fault output is used and how it should be controlled.
Setting
---
Via RF
Q1 (local)
Main menu > Commissioning > Basic configuration > Faults >
Fault output X:
Fault output
1
2

Configure inputs

By closing a contact at the input terminal, the respective input func-
tion can be triggered.
Activate the respective input function by stating from where the cen-
tral apartment unit receives the signal of the input terminal
(---, Via RF / S-Mode, B (local)).
Siemens
Building Technologies
Factory setting
---
---
---
---
Description
Inactive – fault output not required
Relay output Qx of an RRV91...
heating circuit controller used as a
fault output
Relay output Q1 of the central
apartment unit used as a fault output
Factory setting
---
---
Synco 900
Commissioning the system
Your setting
---
Via RF / S-Mode
B (local)
---
Via RF / S-Mode
B (local)
---
Via RF / S-Mode
B (local)
---
Via RF / S-Mode
B (local)
Your setting
--- (none)
Via RF
Q1 (local)
--- (none)
Via RF
Q1 (local)
27/88
CE1C2707en
05.07.2007