Technical data

Power supply

Operational data

Environmental
conditions

Norms and standards

Environmental
compatibility
6/8
Siemens
Building Technologies
Operating voltage
Frequency
Power consumption
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line re-
quired under all circumstances
Control outputs Q1, Q2, Q3
Rating
Control output Y11, Y21 (N.O. contacts)
Rating
Signal input B1 for return air sensor
Status input D1 and GND
Contact sensing
Insulation against mains
Perm. cable length with copper cable 1.5 mm
for connection to terminals B1, B2 and D1
Setpoint setting range
Max. control deviation at 25 °C
Switching differential in heating mode SDH
(selectable)
Switching differential in cooling mode SDC
(selectable)
Dead zone in normal operation
Setpoint «Energy saving mode
Setpoint « Energy saving mode
Setpoint «Standby
»
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
EU Conformity (CE)
RCM Conformity
Safety class
Pollution class
Degree of protection of housing
The product environmental declaration CE1E3020
ronmentally compatible product design and assessments (RoHS compli-
ance, materials composition, packaging, environmental benefit, disposal).
*) The documents can be downloaded from http://siemens.com/bt/download.
Room temperature controller
AC 230 V +10/-15 %
50/60 Hz
max. 6 VA
AC 230 V
max. 600 VA
AC 230 V
max. 300 VA
QAH11.1, Safety class II
NTC resistor 3kΩ at 25°C
SELV DC 6-15 V / 3-6 mA
4 kV
2
80 m
8...30 °C
max. °0.7 K
1 K or 4 K
0.5 K or 2 K
2 K or 5 K
», heating
16 °C
», cooling
28 °C
8 °C
to IEC 60721-3-3
class 3K5
0 ...+50 °C
<95 % r.h.
to IEC 60721-3-2
class 2K3
,25...+70 °C
<95 % r.h.
class 2M2
to IEC 60721-3-1
class 1K3
,25...+70 °C
<95 % r.h.
CE1T3020xx
CE1T3020en_C1
II to EN 60 730-1
normal
IP30 to EN 60 529
*)
contains data on envi-
*)
*)
CE1N3023en
2017-11-14

Hide quick links: