Data Format; Protocol Structure - Siemens Expert Series Operating Note

For tempering units and hot runners
Table of Contents

Advertisement

Data format

6.1
For transmission of block length and checksum, the hexadecimal format is used,
whilst set-points and process values are transmitted in BCD format. For
transmission, hexadecimal values are converted into ASCII. For simplification,
values above 9 (A-F) are coded as 3Ah - 3Fh instead of 41h-46h (ASCII A-F).

Protocol structure

6.2
1
Address
Byte 1:
Byte 2-4:
Byte 5:
Byte 6-n:
Byte n+1,n+2:
g
Hexadecimal numbers are coded in form xxh, e.g. 41h means decimal 65 or 'A'
in ASCII.
Operating note KS 50-1 TCont
2
3
4
Length
Device address of instruments 1 – 32, default 1
• Master → slave (range: B1h...D1h, B0h: reserved)
• Slave → master (range: 31h...51h, 30h: reserved)
Block length; each message contains 3 bytes, which include
(ASCII-coded) the binary number of bytes of the overall message
(including checksum bytes). When receiving, the correct number of
bytes is checked
(range: 30h,30h,37h ... 3Fh,3Fh,3Fh)
Identification marks the message type,(range: 41h, 7Fh), see below
Information bytes, see below
Checksum; every message is completed by 2 checksum bytes, which
are also counted in the block length bytes. The checksum bytes are the
(ASCII-coded) 8 bit wide sum of all bytes of the message including
block length bytes, checksum bytes not included.
(range: 30h,30h...3Fh,3Fh)
5
6
...
Message
Identificaton
15
Communication protocol
n
n+1
n+2
Checksum