Connect The Switching Group Relay - Siemens Synco 900 Mounting And Commissioning

Hide thumbs Also See for Synco 900:
Table of Contents

Advertisement

Main menu > Commissioning > RF connections > Switching groups >
Switching group X > Connect device:
Confirm subentry "Connect device" by pressing the Menu/ok button.
To make the connection, you is prompted to press the binding button
on the device to be connected.
Press the button on the GAMMA wave actuator until the LED on the
actuator starts blinking (approx. 10 seconds). A successful connec-
tion appears on the display of the central apartment unit and is con-
firmed with a beep. The LED on the actuator extinguishes again.
You can connect all actuators of the same switching group,
one after the other, without having to make further entries on
the central apartment unit.
A switching group can be assigned any number of light actu-
ators since they are not entered on the device list of the central
apartment unit.
When all light actuators of a switching group are connected, close the
binding process by pressing the Menu/ok button.
The process is required for every switching group.
For detailed information on commissioning GAMMA wave
components, refer to the documentation covering the GAMMA
wave products.

Connect the switching group relay

Inform the central apartment unit that you want to use a universal
relay output Qx of a heating circuit controller as a switching group
relay:
Main menu > Commissioning > RF connections >
Switching group relay > Switching group X > Connect device:
Confirm subentry "Connect device" by pressing the Menu/ok button.
To make the connection, you is prompted to press the binding button
on the device to be connected.
Select a universal relay output Qx with the channel selection button
(CH) on the heating circuit controller. The LED of the selected chan-
nel blinks. If the selected channel is not yet connected, the connec-
tion LED flashes.
Now, press the multifunction button on the heating circuit controller.
The LED lights up green. When it starts blinking, you can release the
binding button.
A successful connection is shown on the display of the central apart-
ment unit and be confirmed with a beep. Close the binding process
by pressing the Menu/ok button.
Siemens
Building Technologies
Synco 900
Commissioning the system
47/88
CE1C2707en
05.07.2007