Self-learning Room Temperature Controller
5 operating modes, heating / cooling functions and menu selection via roller selector
For the control of the room temperature in:
Room temperature controller with 7-day time switch
When ordering, please give the type reference.
The controller is supplied complete with batteries.
Selection of operating mode | |
Warmer button | |
Colder button | |
Override button | |
Roller selector for the menu, submenu and settings Confirm by pressing | |
Leaving the current menu level and returning to the menu level previously active (the settings currently displayed will be accepted) |
Time of day | |
Room temperature | |
Change batteries (display appears about 3 months before batteries are exhausted) | |
Remote operation active | |
Holiday mode active |
| Automatic mode | |
Comfort mode | ||
Economy mode | ||
Frost protection or overtemperature protection | ||
24-hour mode with one heating or cooling period (heating or cooling period is automatically generated from the current 24-hour program) |
(change only active until the next switching point is reached)
When pressing the + or – button once, the adjusted setpointtemperature will be displayed. It can be readjusted in increments of 0.2°C (max. +/- 4°C). |
In operating modes and , this button can be used to switch from comfort to economy temperature, or vice versa. The selection is maintained until the next switching point is reached or until the operating mode is changed.
Time of day and day | Main menu | Submenu | Settings | ||
Current time of day Current day of week | |||||
Temperature | Main menu | Submenu | Factory settings – heating / cooling | ||
T | Setpoint comfort mode | 19°C | 23°C | ||
Setpoint economy mode | 16°C | 29°C | |||
Setpoint frost or overtemperature protection | 5°C | 35°C | |||
Setpoint economy moderemote operation | 10°C | 30°C | |||
Time switch | Main menu | Submenu | Settings | ||
Selection of day of week, working day, weekend or week | |||||
Selection of the number of heating or cooling periods, max. 3 | |||||
| |||||
Absence | Main menu | Submenu | |||
Entry of holidays or periods of absence. (number of days with economy mode setting / max. 99 days) Temperature setpoint during absence | |||||
Menu-driven heating engineer settings | Main menu | Settings | |||
Sensor calibration | |||||
Setpoint limitation | |||||
Optimum start control for first heating period (in unit of time per 1°C) | |||||
2-position control | |||||
PID mode, self-learning | |||||
PID mode with a switching cycle of 6 or 12 minutes | |||||
Periodic pump run Off / On | |||||
Operating mode heating / cooling |
Temperature setpoints
In the automatic operating modes, temperature setpoints can be individually adjusted for every comfort period and for the continuous operating modes. The temperature setpoint of economy mode is the same in automatic and continuous operation.
Protective function
In the frost or overtemperature protection mode, the room temperature is constantly monitored. If it falls (rises) below (above) the adjusted setpoint, heating / cooling is switched on to maintain the adjusted frost or overtemperature protection setpoint temperature .
The controller generates the 24-hour operating mode from the current 24-hour program. It automatically selects the switch-on time of the first heating / cooling period and the switch-off time of the last heating / cooling period to generate and display a complete heating / cooling period. The comfort temperature used by the controller is the currently stored standard setpoint of the continuous operating mode . The selfgenerated 24-hour operating mode is maintained until another operating mode is selected.
Example
The switching program can be used as a 7-day or 24-hour switching program, depending on programming. It is also possible to select one of the continuous operating modes with which the switching program is not used.
With the 7-day switching program, it is possible to program all days individually, the working days (1-5), the weekend (6-7), or the entire week (1-7).
When a heating / cooling period is programmed, 3 different switching patterns are available.
It is possible to select 1, 2 or 3 heating / cooling periods.
For each heating / cooling period, the start time, end time and comfort setpoint are to be entered. In between heating / cooling periods, it is always the same economy temperature setpoint that is used. This economy temperature setpoint can be adjusted on the temperature menu.
Example with 2 heating periods per day
The holiday function is to be selected on the user menu. Set the start of the holiday period (day of departure/ / day of week), the duration and the temperature setpoint () during your absence. This will enable the controller to maintain the required temperature for a period of up to 99 days. Every midnight, the counter subtracts one day.
When the holiday period is over and the counter reads 00, the controller will resume the operating mode selected last.
Using a suitable remote operating device, the controller can be switched to an independently adjustable economy temperature . Changeover is accomplished by the making of a potentialfree contact connected to terminals T1 and T2. In that case, symbol will appear on the display. When the contact opens, the operating mode selected last will be resumed.
Operation according to the setting made on the controller | Continuously remote operation economy temperature |
Remote operating devices
Suitable remote operating devices:
telephone modem, manual switch, window switch, presence detector, central unit, etc.
Accessing
To access the heating engineer level, keep the warmer and colder buttons depressed and simultaneously roll the roller selector away from the display and then toward the display.
Sensor calibration
CAL
If the displayed temperature does not correspond to the effective room temperature, the temperature sensor can be recalibrated (recalibration to be made on the heating engineer level).
The displayed temperature can be matched to the effective room temperature in increments of 0.2°C (max. ±2°C).
Limitation of setpoint
Minimum setpoint limitation of 16°C prevents undesired heat transfer to neighboring apartments in buildings with several heating zones. The setting is to be made on the heating engineer menu.
Optimum start control
Optimization brings forward the switch-on point of the first heating period such that the adjusted setpoint will be reached at the desired time.
The setting depends on the type of controlled system, that is, on heat transmission (type of piping system, radiators), building dynamics (building mass, insulation), and heat output (boiler capacity, flow temperature).
Optimum start control is switched off at
Example with an actual room temperature of 18°C and a setpoint of 20°C:
Control
The REV23 is a 2-position controller providing PID mode. The room temperature is controlled through the cycling switching of an actuating device.
The controller generates the positioning signals depending on the deviation of the adjustable setpoint from the actual value acquired by the built-in temperature sensor. The rate of response to the deviation depends on the selected control algorithm:
Self-learning mode
The controller is supplied with an active self-learning operating mode, enabling it to automatically adapt to the controlled system (type of building construction, type of radiators, size of the rooms, etc.). After a certain learning period, the controller optimizes its parameters and then operates with the learned parameters.
Exceptions
In exceptional cases, in which the self-learning mode may not be ideal, it is possible to select PID 12, PID 6 or 2-Pt mode:
PID 12 mode
Switching cycle of 12 minutes for normal or slow controlled systems (massive building structures, large spaces, cast-iron radiators, oil burners).
PID 6 mode
Switching cycle of 6 minutes for fast controlled systems (light building structures, small spaces, plate radiators or convectors, gas burners).
2-Pt mode
Pure 2-position control with a switching differential of 0.5°C (±0.25°C) for very difficult controlled systems with considerable outdoor temperature variations.
Periodic pump run
Protects the pump against seizing during longer off periods. Periodic pump run is activated for one minute every 24 hours at midnight. This function can be selected on the heating engineer menu.
Periodic pump run active: / periodic pump run inactive:
Operating mode heating / cooling
The controller is suited for cooling applications. The function can be selected on the heating engineer menu. The controller comes set for heating operation (refer to factory settings).
Reset functions
User-defined data:
Press the button behind the pin opening for at least one second: this resets the userspecific settings to their default values (the heating engineer settings will not be changed). The clock starts at 12:00. During the reset time, all sections of the display light up, enabling them to be checked.
All user-defined data plus the heating engineer settings:
Press the button behind the pin opening together with the warmer and colder buttons for at least one second.
After this reset, all factory settings will be reloaded (also refer to section "Factory settings").
Battery change
About 3 months before the batteries are exhausted, the battery symbol appears on the display, but all functions will be fully maintained. When changing the batteries, the current data will be retained for a maximum of one minute.
Controller
The REV23 has a plastic housing with a large display and easily accessible operating elements. The controller is removed from its base by sliding it upward. It is thus possible to replace the two 1.5 V alkaline batteries type AA in the compartment at the rear of the controller.
Base
The base can be fitted to most types of commercially available recessed conduit boxes or directly on the wall for wiring. The base only houses the terminals for the electrical connection between the controller and connected devices. The entire electronics (including the relay with a potentialfree changeover contact) are accommodated in the controller.
Engineering
Mounting and installation
Commissioning
General unit data | Operating voltage | DC 3 V |
Batteries (alkaline AA) | 2 x 1.5 V | |
Battery life | approx. 2 years | |
Backup for batter change | max. 1 min | |
Switching capacity of relay | ||
Voltage | AC 24...250 V | |
Current | 6 (2.5) A | |
Safety class | II to EN 60 730-1 | |
Sensing element | NTC 10 kΩ ±1% at 25°C | |
Measuring range | 0...50°C | |
Time constant | max. 10 min | |
Setpoint setting ranges | ||
Normal temperature | 5...29°C | |
Economy temperature | 5...29°C | |
Frost protection temperature | 5...29°C (factory setting 5°C) | |
Resolution of settings and display | ||
Setpoints | 0.2°C | |
Switching times | 10 min | |
Measurement of actual value | 0.1°C | |
Display of actual value | 0.2°C | |
Display of time | 1 min | |
Norms and standards | CE conformity | |
Electromagnetic compatibility | 89/336/EEC | |
Low voltage directive | 73/23/EEC | |
C-Tick | N474 | |
Product standards | Automatic electrical controls for household and similar use | EN 60 730-1 |
Electromagnetic compatibility | ||
Immunity | EN 50082-1 | |
Emissions | EN 50081-1 | |
Environmental conditions | Operation | |
Climatic conditions | class 3K3 to IEC 60 721-3 | |
Perm. ambient temperature | 5...40°C | |
Humidity | < 85% r.h. | |
Storage and transport | ||
Climatic conditions | class 2K3 to IEC 60 721-3 | |
Ambient temperature | -25...+70°C | |
Humidity | < 93% r.h. | |
Mechanism | class 2M2 to IEC 60 721-3 | |
Weight | Incl. package | 0.33 kg |
Color | Housing | signal-white RAL9003 |
Base | grey RAL7038 | |
Size | Housing | 140 x 104.5 x 30 mm |