Select The Commissioning Menu; Configure Rooms - Siemens Synco 900 Mounting And Commissioning

Hide thumbs Also See for Synco 900:
Table of Contents

Advertisement

Select the Commissioning menu

From the "Main menu" of the central apartment unit, select submenu
"Commissioning" and confirm the selection by pressing the Menu/ok
button.
Caution!
Plant stops
Commissioning
Basic configuration...
RF connections...
Device list...
Bus communication...

Configure rooms

Activate the required rooms by selecting a room type other than "---".
Main menu > Commissioning > Basic configuration > Rooms >
Room X > Room type:
The following room types are available:
Room type
---
Radiator heating slow
Radiator heating fast
Floor heating slow
Floor heating fast
User-defined
No heating
Usually, the standard room types suffices. Customize settings
only in plants with greatly differing control behavior.
16/88
Siemens
Building Technologies
Then, you are informed that the
plant stops. Confirm by pressing
the Menu/ok button to shut down
the plant and to go to the "Com-
missioning" menu.
You are now on the
"Commissioning" menu – the plant
has been stopped. It is switched
on again only when manually
quitting the "Commissioning"
menu by pressing the Esc button
(no timeout).
Description
Inactive – all relevant room information
and all operating lines are hidden
Radiator heating in buildings with
massive walls, heavy construction
Radiator heating in buildings with light
walls, light construction
Floor heating in buildings with massive
walls, heavy construction and massive
floor construction
Floor heating in buildings with light
walls, light construction and light floor
construction
Control parameters can be manually
set
For rooms with no heating but
equipped with window contacts or a
smoke detector
Synco 900
Commissioning the system
CE1C2707en
05.07.2007

Advertisement

Table of Contents
loading