UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Table 9-2 Power backup specifications
Item
One internal
battery string
for one UPS
One internal
battery string
+ one external
battery pack
for one UPS
One internal
battery string
+ two
external
battery packs
for one UPS
One internal
battery string
+ three
external
battery packs
for one UPS
Issue 02 (2016-07-28)
Load
UPS2000-G-1KR
TS (min)
100%
4.0
75%
6.5
50%
12.5
25%
24.5
100%
24
75%
38.5
50%
65
25%
127.4
100%
N/A
75%
N/A
50%
N/A
25%
N/A
100%
N/A
75%
N/A
50%
N/A
25%
N/A
The battery pack (ESS-24V12-9*3AHBPVBB01) for 1 kVA UPS contain three group battery strings.
The battery pack (ESS-48V12-9*2AHBPVBB01) for 2 kVA UPS contain two group battery strings.
The battery pack (ESS-72V12-9AHBPVBB01) for 3 kVA UPS only contain one group battery
string.
The 1 kVA UPS is allowed a maximum of one battery pack (ESS-24V12-9*3AHBPVBB01) in
parallel. The 2 kVA UPS is allowed a maximum of one battery pack (ESS-48V12-9*2AHBPVBB01)
in parallel. The 3 kVA UPS is allowed a maximum of three battery packs
(ESS-72V12-9AHBPVBB01) in parallel.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
UPS2000-G-2KR
UPS2000-G-3K
TS (min)
RTS (min)
4.0
4.5
6.5
7.3
11.5
13.0
26.0
29.9
14.0
11.0
22.5
17.5
36
28.0
85.5
58.8
N/A
17.5
N/A
28.5
N/A
47.0
N/A
104.0
N/A
27.0
N/A
41.5
N/A
68.0
N/A
141.0