Huawei UPS2000-G-1KRTS User Manual page 36

Hide thumbs Also See for UPS2000-G-1KRTS:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Alarm
Alarm
Alarm
ID
Cause
Name
ID
26
1
Battery
underv
oltage
Battery
time
low
warnin
g
Issue 02 (2016-07-28)
Alarm
Alarm
Severity
Clear
Mode
after the
UPS
transfers
to battery
mode.
Critical
This alarm
must be
manually
cleared.
This alarm
Minor
is
automatic
ally
cleared.
Minor
This alarm
is
automatic
ally
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
14.7 V.
battery
undervoltage
alarm is
generated, the
UPS
automatically
transfers to
normal mode
and starts the
charger for
charging.
The
This alarm is
voltage of
generated
each
because there
battery is
are more
lower than
batteries than
5 V (when
required. The
the UPS is
impact is as
started).
follows:
If battery
packs are
connected
before the
startup, the
UPS fails
to start.
If battery
packs are
connected
during the
running of
the UPS,
the UPS
transfers to
bypass
mode.
The
The power
voltage of
supply from
each
the UPS is not
battery is
affected.
lower than
11.28 V.
Indicate
The power
battery
supply from
discharge
the UPS is not
time
affected.
remain is
short, the
4 Setting Control Panel
Repair Proposal
Possible cause:
The actual
number of
batteries does not
meet
requirements.
Measure: Check
that the actual
number of
batteries meets
requirements.
Possible cause:
The mains is
abnormal, and
the batteries are
overdischarged.
Measure:
Connect to the
mains in
non-battery test
state.
Possible cause:
The mains is
abnormal, and
the batteries
discharge time is
coming.
30