Huawei UPS2000-G-1KRTS User Manual page 41

Hide thumbs Also See for UPS2000-G-1KRTS:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Alarm
Alarm
Alarm
ID
Cause
Name
ID
42
36
Interna
l fault
42
42
Interna
l fault
66
1
Output
overloa
d
66
2
Output
overloa
d
Issue 02 (2016-07-28)
Alarm
Alarm
Severity
Clear
Mode
Minor
This alarm
is
automatic
ally
cleared.
Critical
This alarm
must be
manually
cleared.
Minor
This alarm
is
automatic
ally
cleared.
Minor
This alarm
is
automatic
ally
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
not start or
clear the fault.
The
The power
charger has
supply from
no output.
the UPS is not
affected.
The
The UPS
voltage of
transfers to
each
bypass mode.
battery
decreases
to below
10 V when
the charger
has no
output and
the UPS
inverter is
started.
The
The power
inverter
supply from
output load
the UPS is not
is more
affected.
than 105%
of the rated
load.
The bypass
The power
output load
supply from
is more
the UPS is not
than 110%
affected.
of the rated
load.
4 Setting Control Panel
Repair Proposal
Possible cause:
The fan is
abnormal.
Measure: Clean
up the foreign
matter around the
fan. If the alarm
persists, contact
the dealer or
Huawei technical
support.
Possible cause: The
internal connection
of the charger is
abnormal. Measure:
Contact the dealer or
Huawei technical
support.
Possible cause: The
charger switching
transistor is faulty.
Measure: Contact
the dealer or Huawei
technical support.
Possible cause: The
load exceeds the
rated loading
capacity of the
inverter.
Measure: Lower the
load or replace the
UPS with a UPS
with a larger
capacity.
Possible cause: The
load exceeds the
rated loading
capacity of the
bypass.
Measure: Lower the
35