UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Display
The lowest input voltage in bypass mode should be lower than the lowest input voltage in ECO mode.
Display
Display
Issue 02 (2016-07-28)
06: Set the battery capacity.
07: Set the discharge time limit.
08: Enable or disable the ECO mode.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Setting Control Panel
Setting
Press ▼ or ▲ to adjust and set the lowest
input voltage in bypass mode.
170–220: The value range is 170 V AC to
220 V AC, the default value is 170 V AC.
Setting
Press ▼ or ▲ to adjust and set the UPS
battery capacity.
9–999: Set the UPS battery capacity in the
range of 9 Ah to 999 Ah. (The default value
is 9 Ah and up configurable.)
Setting
Set the backup time limit.
0–999: Set the battery backup time in
battery mode. The value ranges from 0
minutes to 999 minutes.
0: The backup time limit is canceled
(default value).
24