Huawei UPS2000-G-1KRTS User Manual page 39

Hide thumbs Also See for UPS2000-G-1KRTS:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Alarm
Alarm
Alarm
ID
Cause
Name
ID
l fault
42
27
Interna
l fault
Interna
l fault
42
28
Interna
l fault
Issue 02 (2016-07-28)
Alarm
Alarm
Severity
Clear
Mode
automatic
ally
cleared.
Critical
This alarm
must be
manually
cleared.
Critical
This alarm
must be
manually
cleared.
Critical
The first
three
alarms are
cleared
automatic
ally. Later
alarms, if
generated,
must be
cleared
manually.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
the
restored to the
EEPROM.
factory
settings. If this
alarm is
generated, the
customer
needs to
replace the
UPS.
The
If this alarm is
inverter
generated
voltage is
during the
higher than
running of the
1.15 times
UPS, the UPS
the rated
transfers to
output
bypass mode.
voltage.
The
If this alarm is
inverter
generated
output
during the
voltage is
running of the
lower than
UPS, the UPS
75% of the
transfers to
rated
bypass mode.
output
voltage,
and the
output
current is
lower than
60% of the
rated
output
current.
The
If this alarm is
inverter
generated
output
during the
voltage is
running of the
lower than
UPS, the UPS
100 V.
transfers to no
output. After
20 minutes,
the UPS
automatically
starts the
inverter. If this
alarm persists,
the UPS then
transfers to no
4 Setting Control Panel
Repair Proposal
EEPROM is faulty.
Measure: Contact
the dealer or Huawei
technical support.
Possible cause: The
inverter is faulty.
Measure: Contact
the dealer or Huawei
technical support.
Possible cause:
The output load
types are not
supported or the
load exceeds the
specifications.
Measure: Check
whether the load
types are
supported and
reduce the output
load. Then,
manually clear
the alarm and
33