Huawei UPS2000-G-1KRTS User Manual page 42

Hide thumbs Also See for UPS2000-G-1KRTS:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Alarm
Alarm
Alarm
ID
Cause
Name
ID
66
3
Output
overloa
d
Issue 02 (2016-07-28)
Alarm
Alarm
Severity
Clear
Mode
Critical
This alarm
must be
manually
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
In
For battery
battery
mode, the
mode,
UPS
this
transfers to
alarm is
no output
generat
mode.
ed
If the UPS
when
transfers
the load
from
exceeds
normal
the
mode to
rated
bypass
load.
mode three
In
times
normal
within 20
mode,
minutes,
when
the UPS is
the
locked in
bypass
bypass
input is
mode.
normal,
For normal
this
mode, the
alarm is
UPS
generat
transfers to
ed
no output
when
mode.
the UPS
transfer
s to
normal
mode
three
times
within
20
minutes
after the
UPS
transfer
s from
normal
mode to
bypass
mode.
In
normal
4 Setting Control Panel
Repair Proposal
load or replace the
UPS with a UPS
with a larger
capacity.
Possible cause: The
load exceeds the
rated loading
capacity of the
inverter.
Measure: Lower the
load or replace the
UPS with a UPS
with a larger
capacity.
36