Huawei UPS2000-G-1KRTS User Manual page 38

Hide thumbs Also See for UPS2000-G-1KRTS:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Alarm
Alarm
Alarm
ID
Cause
Name
ID
42
17
Interna
l fault
42
18
Interna
l fault
42
24
Interna
Issue 02 (2016-07-28)
Alarm
Alarm
Severity
Clear
Mode
Critical
This alarm
must be
manually
cleared.
Critical
This alarm
must be
manually
cleared.
Minor
This alarm
is
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
UPS fails to
start.
The bus
If this alarm is
voltage is
generated
higher than
during the
450 V.
running of the
UPS, the UPS
transfers to
bypass mode.
The bus
If this alarm is
voltage is
generated
lower than
during the
260 V.
running of the
UPS, the UPS
transfers to
bypass mode.
An error
All UPS
occurs in
parameters are
4 Setting Control Panel
Repair Proposal
repair.
Possible cause:
The mains has
experienced a
transient high
voltage.
Measure: Rectify
the fault and
restart the UPS.
Possible cause:
The output
supplies power to
special loads
such as the
inductive and
rectification
loads.
Measure: Check
that the load
types are
supported by the
UPS.
Possible cause:
The hardware is
damaged.
Measure: Contact
the dealer or
Huawei technical
support.
Possible cause:
The hardware is
damaged.
Measure: Contact
the dealer or
technical
support.
Possible cause:
An overload
occurred when
the input voltage
was low.
Measure: Rectify
the fault and
restart the UPS.
Possible cause: The
32