Set the voltage level based on the actual output voltage. The voltage level can be set to
200 V, 208 V, 220 V, 230 V (default), or 240 V.
Figure 5-2 Setting the output voltage
Set the system output frequency based on the rated frequency. The values include 50 Hz,
60 Hz, and AUT (default).
Figure 5-3 Setting the system output frequency
Set the battery capacity to the total capacity of all batteries actually connected. The
default value is 9 Ah for the UPS, and the value can range from 9 Ah to 999 Ah.
Figure 5-4 Setting the battery capacity
Start the UPS to inverter mode.
Hold down the ON/MUTE button on the front panel for over 5 seconds to make the UPS
transfer to inverter mode output. The default value is 230 V.