Huawei UPS2000-G-1KRTS User Manual page 34

Hide thumbs Also See for UPS2000-G-1KRTS:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
Alarm
Alarm
Alarm
ID
Cause
Name
ID
2
Bypass
freque
ncy
abnor
mal
14
1
Startup
timeou
t
Issue 02 (2016-07-28)
Alarm
Alarm
Severity
Clear
Mode
Minor
This alarm
is
automatic
ally
cleared.
Critical
This alarm
must be
manually
cleared.
Minor
This alarm
is
automatic
ally
cleared.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The bypass
The UPS
frequency
remains in the
is outside
current state.
the bypass
If the UPS
frequency
works in
range.
bypass mode,
it transfers to
standby mode
and has no
output.
The
If this alarm is
inverter
generated
output
during the
voltage is
running of the
not within
UPS, the UPS
± 2 V of the
transfers to
rated
bypass mode.
output.
Discharge
The UPS fails
ends for
to start.
the UPS in
battery
mode, or
the battery
voltage is
lower than
the
minimum
startup
voltage
(11.28 V)
for the
UPS in
4 Setting Control Panel
Repair Proposal
the bypass input
recovers.
Possible cause: The
bypass input
frequency is
abnormal.
Measure: Check
whether the bypass
input frequency
exceeds the
configured range. If
yes, change the
range or wait until
the bypass input
recovers.
Possible cause:
The bypass
loading capacity
exceeds the rated
load of the
inverter.
Measure: Reduce
the output load,
manually clear
the alarm, and
restart the UPS.
Possible cause:
An internal fault
has occurred.
Measure: Contact
the dealer or
Huawei technical
support.
Possible cause: The
battery voltage is
low or the batteries
are damaged after
EOD.
Measure: Wait for
the batteries to
recover or contact
the battery supplier
to replace the
batteries.
28