Display
The CF frequency conversion mode takes priority over the ECO mode. If the CF frequency conversion
mode is enabled, the ECO mode cannot be enabled.
Display
Display
The highest input voltage in bypass mode should be higher than the highest input voltage in ECO mode.
Issue 02 (2016-07-28)
03: Enable or disable the bypass mode.
04: Set the highest input voltage in bypass mode.
05: Set the lowest input voltage in bypass mode.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Setting Control Panel
Setting
Enable or disable the frequency conversion
mode.
50: The output frequency is always 50 Hz,
and the frequency conversion mode is
enabled.
60: The output frequency is always 60 Hz,
and the frequency conversion mode is
enabled.
AUT: The frequency conversion mode is
disabled (default value).
Setting
Enable or disable the bypass function.
ENA: Enables the bypass mode.
DIS: Disables the bypass mode (default
value).
Setting
Press ▼ or ▲ to adjust and set the highest
input voltage in bypass mode.
230–264: The value range is 230 V AC to
264 V AC, the default value is 264 V AC.
23