Alarm
Alarm
Alarm
ID
Cause
Name
ID
22
1
Battery
discon
nected
25
1
Battery
overvo
ltage
Issue 02 (2016-07-28)
Alarm
Alarm
Severity
Clear
Mode
Minor
This alarm
is
automatic
ally
cleared.
Critical
This alarm
must be
manually
cleared.
This alarm
Minor
is
automatic
ally
cleared
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
normal
mode.
Batteries
The power
are not
supply from
connected,
the UPS is not
connected
affected.
improperly,
or
damaged.
The
This alarm is
voltage of
generated
each
because there
battery
are more
exceeds 15
batteries than
V (when
required. The
the UPS is
impact is as
started).
follows:
If battery
packs are
connected
before the
startup, the
UPS fails
to start.
If battery
packs are
connected
during the
running of
the UPS,
the UPS
transfers to
bypass
mode.
The
The UPS
voltage of
automatically
each
transfers to
battery
battery mode.
exceeds
When the
4 Setting Control Panel
Repair Proposal
Possible cause:
No batteries are
connected.
Measure:
Connect
batteries.
Possible cause:
The batteries are
in poor contact.
Measure: Check
the battery cable
connection. If
battery cables are
loose, connect
them securely.
Possible cause:
The actual
number of
batteries does not
meet
requirements.
Measure: Check
that the actual
number of
batteries meets
requirements.
Possible cause:
The charger is
abnormal.
Measure: Check
that the charger
voltage is normal
immediately after
the batteries are
disconnected.
29