5.4.2 Sensor Cable Specification
The minimum requirements are outlined in the following table. Cables supplied by Goyen | Mecair meet these
requirements.
Type
Conductor size
Current rating
Working voltage
Cable shielding
Resistance
Compliance
INSTALLATION AND OPERATION MANUAL – OWNER'S RECORD FFA MANUAL – FILTER FAILURE ALARM
4-core (2-pair) cable
0 5 mm² (16/0.2)
1 A r.m.s (max. per core)
max. 440 V r.m.s
Flame retardant PVC outer sheath (∅7.9 mm), with overall tinned copper, braided, or foil screen
Note: for electrically noisy environments the use of a braided, screened cable is recommended.
For very noisy environments use a cable with multiple layers of foil and braid shielding.
<40 Ω/km (12.192 Ω/kft), recommended for long cable runs
BS5308 part 2, type 1
13