Sensor Cable Specification - Pentair Goyen Mecair FFA Installation And Operation Manual

Filter failure alarm
Table of Contents

Advertisement

5.4.2 Sensor Cable Specification

The minimum requirements are outlined in the following table. Cables supplied by Goyen | Mecair meet these
requirements.
Type
Conductor size
Current rating
Working voltage
Cable shielding
Resistance
Compliance
INSTALLATION AND OPERATION MANUAL – OWNER'S RECORD FFA MANUAL – FILTER FAILURE ALARM
4-core (2-pair) cable
0 5 mm² (16/0.2)
1 A r.m.s (max. per core)
max. 440 V r.m.s
Flame retardant PVC outer sheath (∅7.9 mm), with overall tinned copper, braided, or foil screen
Note: for electrically noisy environments the use of a braided, screened cable is recommended.
For very noisy environments use a cable with multiple layers of foil and braid shielding.
<40 Ω/km (12.192 Ω/kft), recommended for long cable runs
BS5308 part 2, type 1
13