Installing the Device
2.5.1 Connecting AC or DC Power
2.5.1

Connecting AC or DC Power

To connect a single high AC, high DC or low DC power supply to the device, do the
following:
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the metal jumper.
This metal jumper connects transient suppression circuitry to chassis ground and
must be removed in order to avoid damage to transient suppression circuitry during
testing.
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to a DC power supply terminal block. Damage to
the power supply may occur.
Note
Terminals 5 and 7 (POWER 2) are reserved for the external PoE power supply. For in-
formation about connecting the external PoE power supply, refer to
ternal PoE Power (Page
1.
2.
3.
14
Equipment must be installed according to applicable local wiring codes and stan-
dards.
CAUTION
CAUTION
16)".
Remove the terminal block cover.
Identify the internal power module (POWER 1 or POWER 2) appropriate for the
power supply (AC or DC).
Use these screws along with #6 ring lugs to secure the wires to the terminal
block.
Note
For wiring options, refer to
"Wiring Examples (Page
"Connecting Ex-
18)".
RUGGEDCOM RSG2100P
Installation Manual, 01/2020, C79000-G8976-1041-16