FULTON Vantage VTG Series Installation And Operation Manual page 18

Condensing hydronic boilers
Hide thumbs Also See for Vantage VTG Series:
Table of Contents

Advertisement

INSTALLATION
Figure 5 Notes:
 Header must be level or slightly pitched toward the drain.
 Header material to be galvanized steel or 316L stainless.
 Header should be taken to the lowest point possible and
at least 5.5 inch (14.2 cm) drop from 1.5 inch (38.1 mm)
condensate drain kit/trap outlet.
 1.5 inch (38.1 mm) condensate drain kit/trap outlet is never
to be above 1 inch boiler condensate outlet.
 For multiple boiler installation, maintain and minimum pipe
size of 1 inch (25.4 mm) for the header piping.
 The maximum number of units to attach per condensate
drain kit is 12mm BTU total.
2-12
FIGURE 5 - CONDENSATE DRAIN PIPING FOR VANTAGE BOILERS
SIDE VIEW
VTG-IOM-2013-0815
0.25" (U.S.) TAPPING
PROVIDED FOR WATER
CONNECTION TO MAINTAIN
WATER SEAL
Detail A
SECTION 2
Detail A
(condensate drain kit)
5.5 INCH (14.2 CM)
MINIMUM
© The Fulton Companies 2013