FIGURE 8 - OIL PUMP LOCATION (VTG-2000 TO VTG-4000)
FIGURE 9 - OIL PUMP DETAILS (VTG-2000 TO VTG-4000)
2-16
VTG-IOM-2013-0815
Figure 9 Notes
Characteristic
1
Suction
2
Return
3
Pressure Gauge Attachment
4
Vacuum Gauge Attachment
5
Pressure Regulator
6
Outlet to Burner
Minimum Delivery Rate at 174
PSI Pressure
Delivery Pressure Range
Maximum Suction
Oil Viscosity Range
Maximum Fuel Oil
Temperature
Maximum Suction and Return
Pressure
Pressure Calibration at the
Factory
Filter Mesh Width
SECTION 2
Connection
3/8" NPT (Piped in the Field)
3/8" NPT (Piped in the Field)
G 1/8" (Completed at Factory)
G 1/8" (Completed at Factory)
¼" NPT (Completed at Factory)
54 GPH (204.41 LPH)
145 – 290 PSI (997.7 - 1999.5 k Pa)
13 " Hg
2.8 – 75 cSt
140 F (60 C)
29 PSI (199.9 kPa)
198-200 PSI (1365 - 1379 kPa)
0.006 Inches (0.15 mm)
© The Fulton Companies 2013