AXIS A1601 Network Door Controller
System configuration
Access time – Set the number of seconds the door shall remain unlocked after access has been granted. The door remains
unlocked until the door has been opened or until the set time has been reached. The door will lock when it closes regardless
of whether the access time has expired or not.
Long access time – Set the number of seconds the door shall remain unlocked after access has been granted. Long access
time overrides the already set access time and will be enabled for users with long access time selected.
Select Door monitor to make the following door time options available:
Open too long time – Set the number of seconds the door is allowed to stay open. If the door is still open when the set
time has been reached, the door open too long alarm is triggered. Set up an action rule to configure which action the
open too long event shall trigger.
Pre-alarm time – A pre-alarm is a warning signal that is triggered before the open too long time has been reached. It
informs the administrator and warns, depending on how the action rule has been set up, the person entering the door
that the door needs to be closed to avoid the door open too long alarm to go off. Set the number of seconds before the
door open too long alarm is triggered the system shall give the pre-alarm warning signal. To disable the pre-alarm, set
the pre-alarm time to 0.
For information about how to set up an action rule, see How to set up action rules on page 21.
About lock options
The following lock circuit options are available:
Relay – Can only be used on one lock per door controller. If two doors are connected to the door controller, a relay can
only be used on the lock of the second door.
None – Only available for Lock 2. Select if only one lock will be used.
The following lock monitor options are available for single-door configurations:
Lock monitor – Select to make the lock monitor controls available. Then select the lock that shall be monitored. A lock
monitor can only be used on double-lock doors and cannot be used if two doors are connected to the door controller.
-
Open circuit = Locked – Select if the lock monitor circuit is normally closed. The lock monitor gives the door
unlocked signal when the circuit is closed. The lock monitor gives the door locked signal when the circuit is open.
-
Open circuit = Unlocked – Select if the lock monitor circuit is normally open. The lock monitor gives the door
unlocked signal when the circuit is open. The lock monitor gives the door locked signal when the circuit is closed.
How to configure readers and REX devices
When you have configured the door monitors and locks in the new hardware configuration, you can configure the readers and
request to exit (REX) devices.
1. If a reader will be used, select the checkbox and then select the options that match the reader's communication protocol.
13