Chapter 13 Mounting and Wiring

13.1 Mounting the Module

2]
1]
1]
2]

13.2 Wiring to the Power Module

100 V AC
∼ 200 V AC
Leak
breaker
Noise
filter
Insulation
transformer
with shield
3]
EH-150
POWER
HITACHI
PORT
1
PORT
2
(1) Mounting
1]
Hook the claw at the lower section of the module
to the hole in the base.
2]
Press in the upper side of the module until it
clicks.
Note 1:
After mounting the module, check to make
sure it does not come out.
(2) Removing
1]
Push in the lock button.
2]
While the lock button pushed in, pull the top of
the module toward the front.
3]
Raise it toward the top and pull it out.
(1) For power supply wiring, use a cable of 2
mm
or more to prevent a voltage drop.
2
(2) The function ground terminal (FE terminal)
should use cable of 2 mm
0 1
D grounding (100 Ω or less). The
4 5
8 9
12 13
appropriate distance for ground cable is
within 20 m.
1]
Grounding of instrumentation panel
and relay panel can be shared.
2]
Avoid joint grounding with equipment
that may generate noise such as
high-frequency heating furnace, large
scale power panel (several kW or more),
thyristor exchanger, electric welders,
etc.
3]
Be sure to connect a noise filer (NF) to
the power cable.
(3) The terminal screw is an M3. When wiring,
tighten screws within a torque range of 0.49
to 0.78 N·m.
(4) Use the same power supply system for the
basic and expansion units.
13-1