Integrated Power Reset Interval (INTEG)
(12)
Specifies the interval for measuring integrated power.
The range of selection (Options):
OFF / 30min./ 1h (hr.) / 24h
Setting Value
OFF
30min.
1h
24h
Initial value:
OFF
Note
When you press the MODE key and change the operation mode after changing the set value
on ZN-CTX21, the unit resets the setting and restarts, clearing the ranking.
Important
With the ZN-CTX21, only the integrated power is reset on the display, not the integrated
power that is output to a file.
(13)
The Number of Channels to Use (USECH)
Specifies the number of channels to use. The same number of dedicated CTs must be set.
The range of selection (Options):
1CH / 2CH / 3CH
Initial value:
1CH
Measurement Target Circuit (TYPE)
(14)
Select the phase and wire configuration of the circuit to be measured. The items displayed for
selection varies depending on the number of channels to use (USECH).
The range of selection (Options):
1P2 / 1P3 / 3P4
Number of Channels (USECH)
1CH
2CH
3CH
Initial value:
3P3
The unit continuously measures the integrated power without resetting
the value to zero.
The unit measures the integrated value at the interval of 30 minutes; at 0
and 30 minutes of every hour (0:00 to 0:30; 0:30 to 1:00; 1:00 to 1:30...).
The unit measures the integrated value at the interval of one hour; at 0
minutes of every hour (0:00, 1:00, 2:00...).
The unit measures the integrated value at the interval of 24 hours; at
0:00 of every day.
1P2 (Single-phase, two-wire) / 3P3 (Three-phase, three-wire)
1P3 (Single-phase, three-wire) / 3P3 (Three-phase, three-wire)
3P4 (Three-phase, four-wire)
4-13
3. Check and Preparation
Operation
CTX21
CTX21