Pre-Installation Preparation And Guidelines; Planning Dimensions - Vertiv Liebert CW Installer/User Manual

Thermal management system, 305 kw, 375 kw, 415 kw capacity, 50/60 hz
Table of Contents

Advertisement

2 PRE-INSTALLATION PREPARATION AND GUIDELINES
NOTE: Before installing unit, determine whether any building alterations are required to run piping,
wiring and duct work. Follow all unit dimensional drawings and refer to the submittal engineering
dimensional drawings of individual units for proper clearances.
Refer to Table 1.5 on page 7, and submittal drawings to determine the type of system being installed and
anticipate building alterations, piping and duct work needed.
The unit dimensions, pipe-connection locations, and piping schematics are described in the submittal
documents included in the
Verify that the floor is level, solid and sufficient to support the unit. See Table 2.2 on the next
page,for unit weights.
Confirm that the room is properly insulated and has a sealed vapor barrier.
For proper humidity control, keep outside or fresh air to an absolute minimum (less than 5% of
total air circulated in the room).
Do not install a Liebert® CW in an alcove or at the end of a long, narrow room.
Install the units as close as possible to the largest heat load.
Allow at least the minimum recommended clearances for maintenance and service. See the
appropriate submittal drawings for dimensions.
We recommend installing an under-floor water detection system. Contact your Vertiv
representative for information.

2.1 Planning Dimensions

The unit, floor stand, and plenum dimensions are described in the submittal documents included in the
Submittal Drawings
The following table lists the relevant documents by number and title.
Table 2.1 Dimension Planning Drawings
Document Number
Downflow Units
DPN004862
DPN004900
DPN004870
DPN004869
Floor Stands
DPN004866
Airflow Schematic
DPN004865
DPN004904
2 Pre-installation Preparation and Guidelines
Submittal Drawings
on page 45.
Title
Cabinet and Plenum Dimensional Data, Downflow, Horizontal Discharge
Cabinet and Plenum Dimensional Data, Downflow, Bottom Discharge
Installation and Service Clearance Data, Downflow, Horizontal and Bottom Discharge
Floor planning dimensional data for adjacent units
Floorstand Dimensional Data,
Airflow Schematic, Downflow, Horizontal Discharge
Airflow Schematic, Downflow, Bottom Discharge
on page 45.
11