12 LIEBERT ICOM HARDWARE INSTALLATION

Your unit includes the Liebert iCOM controller. This section describes the installation of connections and
cabling to fully utilize the iCOM features.

12.1 Installing Wired Remote Sensors

Up to 10 remote-sensor modules, installed in the monitored racks and connected to the cooling unit,
provide control and reference input to iCOM and building-management systems. Using remote, rack
sensors combats cooling problems related to recirculation air, uneven rack loading, and air distribution.
Each Liebert iCOM comes with 3 2T sensors standard. Although using and adding additional remote
sensors is optional, we recommend attaching one remote sensor to each rack that the unit is intended to
cool because they allow more efficient and effective operation of the cooling unit.
The sensor array consists of 2T sensors that each have two temperature probes on a 6-ft (1.8-m) probe-
connection cable, Figure 11.5 below, and requires several steps to prepare, connect, and begin monitoring
the racks:
Set DIP switches in each sensor.
Terminate final sensor on CANbus link.
Install sensors on racks.
Install CANbus cabling between sensors.
Connect CANbus cable to the cooling unit.
Configure the sensors in iCOM.
NOTE: The 2T sensor shown in Figure 11.5 below may differ slightly for your system, depending on
equipment installed.
Figure 11.5 2T sensor for rack monitoring

12.1.1 Setting DIP switches and labeling 2T sensors

Tools required:
Small, non-conductive tool to set switches
Small, Phillips-head screw driver to open 2T housing.