Page 1
NetSure™ Mini Control Unit User Manual (UM1M831ANA), Revision B Specification Number: 1M831ANA Model Number: M831A Software Version 6.2.00...
Page 2
This document may contain confidential and/or proprietary information of Vertiv Group Corp., and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without specific authorization from Vertiv Group Corp.
Logging into the Controller via Web Interface Access ............25 Setup Procedures............................... 26 Common Tasks Performed via the Local Keypad and/or Web Interface ..................................35 Procedures ..................................35 Power Split Feature ............................50 Overview .................................... 50 Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 4
Site Information Area (#4 in Figure 18) ..................110 Alarms Area (#5 in Figure 18) ........................ 111 System Status Area (#6 in Figure 18) ................... 112 General ....................................112 Power System Status Tab ..........................112 Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 5
Replacement Procedures .................. 224 Controller Replacement ..........................224 Controller Digital Input and Relay Output Connections ......226 Controller Digital Inputs ..........................226 Controller Relay Outputs ......................... 226 Specifications ....................... 227 Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
(ISO) SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
ALERT! Installation or removal of equipment containing static sensitive components requires careful handling. Before handling any equipment containing static sensitive components, read and follow the instructions contained on the Static Warning Page. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
The Mini Control Unit can also be accessed via SNMP (v2 and v3) or TL1 (over Ethernet). A machine-to- machine HTTP interface is also available. Figure 1 illustrates the various applications that can be used to interface with the Mini Control Unit. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 10
Network MODEM MODEM Ethernet RS232 RS485 (2) Site DC Power System RS485 (1) CAN (1) Mini Control Unit Supervisory Modules … Rect 1 Rect 2 Rect 30 SM-Temp Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Web Interface and consists of the following. Logs can be saved in the .html (Web page) or .txt (text) format. • Alarm History Log: Records 4000 latest alarms. The Web Interface displays the latest 500 items. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Battery charge temperature compensation adds a correction term, related to the temperature of the batteries, to the nominal value of the system voltage. The degree of regulation (TempComp Coeff), expressed in mV/°C/battery string, can be set per battery manufacturer recommendations. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 13
Should the battery current still exceed a higher preset value, an alarm is issued. Battery charge current is limited to the value set in the controller, as long as battery voltage is above 47 VDC. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 14
For manual battery discharge tests as well as for scheduled battery discharge tests, the following parameters must be set: End Test Voltage, End Test Time, and End Test Capacity. See Figure 4. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 15
The batteries are reconnected automatically when commercial AC power is restored and a predetermined DC voltage level is reached. See “LVD Tab Programmable Parameter Descriptions” on page 130 for descriptions of programmable LVD parameters. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
The ECO mode is only enabled upon normal system operation. If any of the following alarms occurs, the system cannot enter or will exit the ECO mode. Current imbalance (only when imbalance current protection is enabled). AC fail. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
When power split is programmed, the controller adjusts rectifier output voltage per load demands to ensure proper sharing between “System A” and “System B”. See Figure 5. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
10M/100M Ethernet port. The communication cable shall be a shielded cable. The Ethernet port is located on the front panel of the controller. This port supports Dynamic Host Configuration Protocol (DHCP) function. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
If a special configuration file is furnished, the controller has capability to receive status information sent from FIAMM SoNick (Sodium Nickel) batteries. See “FIAMM SoNick (Sodium Nickel) Batteries Interface” starting on page 56. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
English If no key is pressed within 5 minutes, the controller selects the default language automatically and then displays the Main Screen. 54.3V 0.0A Main Screen Auto Alarm Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 21
ENT key to enter the selected submenu. NOTE! Repeatedly press the ESC key to return in reverse order level by level from any submenu until the MAIN SCREEN appears. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Minor Alarm minor alarms. Alarm conditions are (Yellow) programmable. Major or The system has one or more active Critical Alarm major or critical alarms. Alarm (Red) conditions are programmable. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Local Menu Navigation Keys and Local Display See “Controller’s Front Panel Menu Navigation Keys and Local Display” on page 22. Local Display Menus Refer to “Local Display Menus” on page 88. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Multiple browsers are supported in the Web Interface. The User can use Internet Explorer, Chrome, Safari, or Firefox. Web Interface Screens Refer to “Web Interface Screens” on page 109. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
164. After entering a valid User Name and Password and clicking LOGIN, the Web Interface "HOMEPAGE" window opens. Refer to “Web Interface Screens” on page 109. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
The default settings for these parameters are shown below. • Link-Local Address: fe80:209:f5ff:fe09:1002/64 • IPv6 Address: 20fa:fffd:fffc:fffb:fffa:fff9:fff8:fff7 • IPv6 Prefix: 0 • IPv6 Gateway: 20fa:1:fffe:ffff:fffe:fffd:ffff:fffe Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 27
The Ethernet port located on the IB4 board can be used to connect the controller to your Local Area Network (LAN). Refer to your system’s documentation for location of the IB4 board (if furnished). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 28
Menu / Settings Icon / Comm Settings. Record the following controller’s IP parameters. If these parameters were not changed, they should be at the default values as shown in the example section below. IPv4 IP Address: Subnet Mask: Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 29
Interface. You will also have to set the properties on your computer (refer to the previous procedure in step 1). When finished, disconnect your computer from the controller and, if necessary, reset your computer network settings as recorded in step 1. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 30
Internet Explorer is used in this procedure, other browsers are similar. Launch “Internet Explorer”. Select Internet Options from the Tools menu. The “Internet Options” window opens. In the “Internet Options” window, select the Connections tab. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 31
Internet Explorer is used in this procedure, other browsers are similar. Launch “Internet Explorer”. Select Internet Options from the Tools menu. The “Internet Options” window opens. In the “Internet Options” window, select the General tab. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 32
Under “Browsing History”, click on the Settings button. The following window opens. In the Settings window, choose “Every time I visit the webpage” and click OK. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 33
Click on Trusted sites. With “Trusted sites” selected, click “Sites”. The following window opens. Uncheck the “Require server verification (https:) for all sites in the zone:” box if https is not being used. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 34
In the Trusted sites window, type or copy the controller URL in the “Add this website to the zone:” box. Click Add. The controller URL is listed in the Websites: box. Click Close. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Main Menu / Sys Inventory / ENT to view Inventory. Web Menu Navigation: System Inventory Menu. Clearing or Resetting Alarms Local Menu Navigation: Main Menu / Settings / Alarm Setting / select alarm to clear or reset. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 36
To enter a Date or Time, press ENT. Use the UP and DOWN keys to choose a character. Press ENT to accept and move to the next character. Continue this process until all characters are entered. Press ENT again to accept the date or time. Press ESC to cancel. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 37
IPv6 Communications Parameters (if Controller not set as DHCPv6)” on page 26. Local Menu Navigation: Main Menu / Settings / Communication / enter parameters. Web Menu Navigation: Advance Settings Menu / Ethernet Tab / enter parameters. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 38
Also enter additional parameters from Web Interface (Settings Menu / Battery Tab / enter parameters) Web Menu Navigation: Settings Menu / Battery Tab / Automatic Equalize (set to Yes) then enter the following parameters. • Equalize Start Current Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 39
See also “Using the Relay Test Feature” on page 46. Local Menu Navigation: None. WEB Menu Navigation: Settings Menu / System Tab / “Auto/Manual” State (change to Manual). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 40
Viewing/Changing the Equalize Voltage Setting Local Menu Navigation: Main Menu / Settings / Batt Settings / EQ Voltage. Web Menu Navigation: Settings Menu / Battery Tab / Equalize Charge Voltage. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 41
For example, if the current limit was set to 100% of combined capacity and a rectifier is added, the new current limit setpoint will be 100% of the combined capacity including the new rectifier. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 42
Settings Menu / System Tab / Under Voltage 1. Setting Under Voltage Alarm 2 Local Menu Navigation: Main Menu / Settings / Other Setting / Under Voltage 2. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 43
If desired, set a temperature sensor set as a battery temperature sensor as the battery temperature compensation sensor. Local Menu Navigation: Main Menu / Settings / Batt Settings / TempComp Sensor. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 44
See above for selecting the Battery Thermal Runaway Management (BTRM) temperature sensor and setting BTRM temperature alarms. Local Menu Navigation: None. Web Menu Navigation: Settings Menu / Battery Tab. Enter values for the following parameters: “BTRM Action” and “BTRM Voltage”. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 45
WEB Menu Navigation: Settings Menu / System Tab / System Current Alarm (Enter a value (in amps). If system current exceeds this value, a system current alarm is issued). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 46
To reset the maintenance timer and clear the maintenance alarm, clear the “maintenance run time”. Local Menu Navigation: None. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 47
Defaults" procedure, you can restore your customized settings by downloading the previously saved “SettingParam.tar” file back into the controller. Prior to changing controller settings, ensure the current "SettingParam.tar" file is backed up. After making changes, create a new backup file. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 48
The “SettingParam.tar” file is deleted. Before restoring the factory default configuration, if you have made any changes to the controller, save the “SettingParam.tar” file (see Backing Up the Controller Configuration on page 47). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 49
Advance Settings Menu / DI Alarms Tab. Relay Outputs Advance Settings Menu / DO (relay) Tab. Shunts Advance Settings Menu / Shunts Tab. Fuses Advance Settings Menu / Fuse Tab. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
When the voltage falls below the float setting minus the DELTA VOLTAGE setting, the controller system will come out of current limit and now deliver the additional current necessary to satisfy Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 51
In lieu of this, if battery charging and battery test functions are implemented in the existing power system, they can remain if signals for starting are connected from the control system of the existing system to the controller system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 52
• Connect the Battery and Battery Return busbars of the controller Power System to the main charge busbars (rectifier side of the shunt) on the parallel power system. Size the cable for the largest current between systems. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 53
Power System / PowerSplit Mode. Set this parameter to “enabled”. Reboot the controller by pressing ESC and ENT at the same time. Navigate to Settings Menu / System / Power System. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 54
Using the Web Interface menus (see “Power Split Tab” on page 181), select the controller digital input connected to the existing systems battery test control circuit. NOTE! Other settings in this menu regarding “Battery Test” are inactive. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 55
(or shut down some of the rectifiers in the existing power system if the capacity of the external dry load bank is not sufficient). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Following software is required for SMCMonitor200 communication for the User’s computer, and is available from FIAMM. • Virtual Com-Port Driver Installation • SMCMonitor200 1.5.3 Software Folder, Containing Folders: Backup, Config, Log, XML Containing Files: SMC Battery Software Interface_So-Nick-48TL200.pdf; SMCMonitor200.exe Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 57
See: Sections 3.3, Battery Front Panel; Section 3.5 Data Cable Connector • Vertiv, NetSure 721 Installation Manual (IM582127000). • Vertiv, SD582127000, Schematic Diagram -48V Power System, (Issue J). • Vertiv, T582127000, Wiring Diagram, Power System, (Issue AN). • Vertiv, SD556166, Schematic Diagram for Interface, (Issue AA).
Page 58
‘.xml’ file is to be used. • Save the new BAUD rate in a .xml file as shown below, then load the file into each battery using the UTILITY-->UPGRADE function of the program: Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Controller TL1 Configuration Webpages are provided in the controller Web interface to configure signal parameters and settings that specify the signal’s TL1 attributes. See “Setting TL1 Parameters” on page 38. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
‘/’. The starting and ending time using this format is specified using field names starttime and endtime. The time is the local time on the controller. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 61
If a key is not present, then the data field in the output is empty. For example, if only ukey3 is specified, the output for the keys would be ,,<ukey3>. If no keys are specified, the output for the keys would be ,,. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Over Load Output overload condition. Check the load. Surge protection device needs Check surge protection device. attention. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 64
IB2-2 Board) failure. Temperature sensor #1 (connected EIB-1 Temp 1 Sensor Fail to EIB-1 Board) failure. Temperature sensor #2 (connected EIB-1 Temp 2 Sensor Fail to EIB-1 Board) failure. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 65
Over Voltage 1 Alarm threshold. Check why system voltage is high. Check the alarm setting. Output voltage is higher than the Over Voltage 2 (24V) Over Voltage 2 Alarm threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 66
High diesel generator ambient Ambient Temp High 2 temperature alarm2. Ambient Sensor Fail Ambient temperature sensor failure. Replace temperature sensor. Relay Test Relay Test in progress. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 67
1. Temperature sensor #1 (connected to IB2-1 board and set as Ambient) IB2-1 Temp1 Low sensing temperature lower than low temperature threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 68
1. Temperature sensor #2 (connected to IB2-2 board and set as Ambient) IB2-2 Temp2 Low sensing temperature lower than low temperature threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 69
1. Temperature sensor #1 (connected to EIB-2 board and set as Ambient) EIB-2 Temp1 Low sensing temperature lower than low temperature threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 70
1. Temperature sensor #8 (connected to SM-Temp 1 and set as Ambient) SMTemp1 Temp8 Low sensing temperature lower than low temperature threshold. … … … Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 71
NOT IMPLEMENTED AT THIS TIME SMS Modem Fail SMS modem has failed. Check why SMS modem failed. Manual State Controller in manual state. SNMP Config Error SNMP configuration error. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 72
NOT IMPLEMENTED AT THIS TIME NOT IMPLEMENTED AT THIS TIME Check communications cables. A rectifier has lost communications Rectifier Communication Fail Reset the Communication Fail alarm. with the controller. Replace the rectifier. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 73
“System B”. The currents from two groups of Battery distribution current Discharge Current Imbalance batteries are not equal. Check the imbalance alarm. batteries. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 74
Check why temperature is high or System Temp1 High 1 temperature higher than high low. temperature threshold 1. Temperature sensor #1 sensing System Temp1 Low temperature lower than low temperature threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 75
1. Temperature sensor #2 (connected to IB2-2 board and set as Battery) IB2-1 Temp2 Low sensing temperature lower than low temperature threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 76
1. Temperature sensor #1 (connected to EIB-1 board and set as Battery) EIB-1 Temp1 Low sensing temperature lower than low temperature threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 77
1. Temperature sensor #2 (connected to EIB-2 board and set as Battery) EIB-2 Temp2 Low sensing temperature lower than low temperature threshold. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 78
1. Temperature sensor #1 (connected to SM-Temp 8 and set as Battery) SMTemp8 Temp1 Low sensing temperature lower than low temperature threshold. … … … Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 79
Activates for the condition selected in the “BTRM Temp Delta Alarm” BTRM Temp Delta parameter. Refer to “Battery Tab Programmable Parameter Descriptions” on page 126 for details. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 80
Battery current is high. Battery Leakage Battery has leakage current. Check the batteries. Low Acid Level Battery has low acid level. Check the batteries. Battery Disconnected Battery disconnection is active. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 81
Distribution voltage is lower than the batteries are being recharged, the Under Voltage 2 Under Voltage 2 Alarm threshold. alarm will cease by itself when battery voltage has increased to the charging level. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 82
LVD Unit Alarms (Low voltage disconnect must be present in system) LVD1 contactor is in disconnect LVD 1 Disconnect mode. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 83
Check why voltage is low. AC3 voltage is below under voltage 2 AC3 Under Voltage 2 threshold. Mains Failure Commercial AC power failure. Check why no commercial AC power. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 84
Fuel Group Communication Fuel tank group communication Check communications cables. Failure failure. SMIO Generic Unit 1 Alarms (SM-IO Module must be present in system) SMIO Failure SMIO has failed. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 85
Replace temperature probe. Temperature Probe 8 Open Probe open. SoNick Battery Alarms Battery Communication Fail Refer to the documentation provided with the FIAMM SoNick (Sodium Nickel) Battery. Low Ambient Temperature Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 86
High Charge Current Warning High Charge Current High Discharge Current Warning High Discharge Current Voltage Unbalance Warning Voltages Unbalance DC Bus Pwr Too Low for Charging Charge Regulation Failure Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 87
Table 4 Alarm Name Alarm Description Action to Correct Capacity Below 12.5% Thermocouples Mismatch Heater Fuse Blown Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
LVD# <= LVR# -2 for 48V, -1 for 24V LVD# <= Test Volt -1 for 48V, -0.5 for 24V * These restrictions will apply even if the function is disabled. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
DOWN Remain 360.0 h to Main Menu RectNum4 Info Screen DOWN 2018-01-01 to Main Menu Float Charge Info Screen Alternates between the date and the time being displayed. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 90
HW Ver: A01 SW Ver: 6.2.01 Info Screen Config: 565565AA File Sys: 1.02 Info Screen 10.201.229.103 Info Screen MAC: 00:09:F5: 18:03:55 Info Screen Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
These instructions describe the complete functionality of the controller. Some functionality is dependent on hardware connected to the controller. Some menu items shown may not be present in the controller used in your system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 92
Sys Inventory Rect #1 Rect #1 DOWN Part Number 1R481000e3 Main Menu DOWN Rectifier Product Ver DOWN DOWN Main Menu Settings SW Version 9.01 DOWN Serial Number ########### Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 93
Used Capacity 0.0% DOWN DC Status DOWN AC Voltage 222 V DOWN AC Feed DOWN AC On/Off DOWN Running Time 3128h DOWN Walk-In Enabled DOWN Serial Number ########## Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 94
Batt Settings DOWN Settings Batt1 Setting DOWN Settings Batt2 Setting DOWN Settings LVD Settings DOWN Settings AC Settings DOWN Settings Other Setting DOWN Settings Communication DOWN Settings Sys Settings Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 95
DOWN Factory default settings are listed in the controller configuration drawing Rects ON Time (C-dwg) furnished with your system. 12min (0 to 255) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 96
Factory default settings are listed in the controller configuration drawing (Yes) (C-dwg) furnished with your system. DOWN ClrBatTestFail (Yes) DOWN ClrCycleAlm (Yes) DOWN Clr AbnlCur Alm (Yes) DOWN Clr Cur lmb Alm (Yes) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 97
Start Interval the controller configuration drawing (C-dwg) furnished with your system. 0sec (0 to 10) DOWN Rect Upgrade Enabled (Disabled / Enabled) DOWN Normal Update (No / Yes) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 98
(43.0 to 53.5) DOWN End Test Volt 45.2V (43.2 to 53.5) DOWN End Test Time 10min (10 to 1440) DOWN EndTestCapacity (0 to 100) DOWN RecordThreshold 0.100V (0.1 to 1) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 99
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the controller configuration drawing (C-dwg) furnished with your system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 100
43.1V (36 to 60) DOWN LVD2 Recon Volt 52.4V (40 to 60) DOWN LVD 2 Time 599min (30 to 1000) DOWN LVD 2 HTD Disabled (Disabled / Enabled) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 101
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the controller configuration drawing (C-dwg) furnished with your system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 102
Reload Config Factory default settings are listed in the controller configuration drawing (Yes) (C-dwg) furnished with your system. DOWN Auto Config (Yes) DOWN Clr Alm Hist (Yes) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Optimization. • Cycle Period: This is the time period that rectifiers are turned on and off to maintain an equal operating time for all rectifiers in the system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
• Float Voltage: Float charge output voltage setting for rectifiers. • EQ Voltage: Equalize charge output voltage setting for rectifiers. • Num Batt Shunts: Sets the number of battery shunts in the system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 105
Float mode until the current Equalize cycle is completed. To return immediately to Float mode, navigate as follows: Main Menu / Settings Icon / Maintenance / “EQ/FLT Control”, and select Float Charge. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
HTD1 and/or HTD2 features are enabled. If this temperature is reached, a disconnect occurs regardless of voltage. • HTD Recon Point: Sets temperature at which a reconnect will occur following a High Temperature Disconnect. • LVD 1: Enables or disables LVD1. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
IP address fails, an alarm is generated. If the acquisition of an IP address is successful, you need to record the IP address automatically acquired by the controller to access the controller via Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
• Reload Config: Restores the controller’s default settings. • Auto Config: Auto configures the controller for the devices connected to it. • Clr Alm Hist: Clears the alarm history. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Controller Specifications Information Area (see page 110.) Site Information Area (see page 110.) Alarms Area (see page 111.) System Status Area (see page 112.) Menu Navigation Area (see page 120.) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Site Information Area (#4 in Figure 18) Site information is displayed here. See Figure 19. Figure 19: System Status Information, System Specifications Information, Controller Specifications Information, and Site Information Areas Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Minor alarms are shaded yellow, major alarms are shaded orange, and critical alarms are shaded red. Figure 20: Alarms Area Arrow Icon Alarm Severity Tabs or All Alarms “Auto Popup” Box Alarm List Collapsed Alarm List Expanded Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Figure 21: Power System Status Tab Alarms or No Alarms Symbol Click here to open up Alarm List. Temperature Reading Click here for Temperature Trend Diagram. System Current Reading Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 113
For example, clicking on the rectifier icon (see Figure 22) opens the rectifier device group status Web page (see Figure 23). Figure 23: Rectifier Device Group Status Web Page Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 114
See Figure 26. Click to go back to the Rectifier Device Group Status Web page. Figure 25: Selecting an Individual Rectifier Settings Page Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 115
Manual mode. Setting returns to original when controller is returned to the Auto mode. • Rectifier ID: Sets the rectifier’s identification number. • AC Feed: Indicates the phase connected to the rectifier’s input. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 116
Displayed on the Battery Device Group Status Web page are the individual batteries installed in the system. Hover the mouse over an individual battery icon to display its status such as "Battery Rating". See Figure 29. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 117
Web page. The actual display of an Individual Battery status is dependent on the controller configuration. Note that FIAMM SoNick (Sodium Nickel) Battery parameters (if in controller configuration) cannot be changed. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 118
• Battery Management: Select Yes to use the battery management feature and No to not use the feature for this battery. • Rated Capacity: Enter the battery string's rated capacity. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
General Status Tab The General Status tab displays general status information. See Figure 33. NOTE! Temperature items are displayed only if temperature probes are connected. Figure 33: General Status Tab Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
NOTE! Some parameters are not available for controller configurations that enable controller capability to receive status information sent from FIAMM SoNick (Sodium Nickel) batteries. Figure 36: Settings Menu Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 122
Then select the “Confirm” button. See Figure 37. In the Time Settings section, click on “Set” to save the change. Figure 37: Manual Date and Time Menu Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 123
• High Load Level1: Sets the High Load Level 1 alarm point (Percentage of total rectifier capacity. When solar converters and rectifiers are both in the system, high load level is based on the capacity of all valid Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 124
(3) minutes. Secondary: Select this option if the power system consists of multiple bays with multiple controllers and this controller is to be a secondary controller. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 125
The system automatically restarts when the signal is removed.) • Audible Alarm Off: Disables the audible alarm. On: When a new alarm occurs, the audible alarm sounds. Press any key to silence the audible alarm. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 126
Bay Alarm led). The choices are: “CR Only”, “CR and MJ”, and “CR, MJ and MN”. Battery Tab Programmable Parameter Descriptions • Equalize/Float Charge Control: Places the system in Equalize Charge or Float Charge mode. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 127
• Number of Battery Shunts: Sets the number of battery shunts that are directly connected to the controller. Factory set and should not be changed unless directed by Vertiv. • Batt1 Rated Capacity: Enter the battery string's rated capacity. After setting the battery capacity, the User should also reset the battery capacity (battery must be fully charged).
Page 128
30% of the battery’s nominal capacity, an alarm will be extended. • Automatic Equalize: Enables or disables the Automatic Equalize Charge feature. When enabled, the following parameters can be set. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 129
• Time 1.0C10: Discharge time with a discharge current of 1.0C10. • Clear Abnormal Bat Current: Clears an abnormal battery current alarm. The only selection is Yes. Once Yes is selected and confirmed, the alarm clears. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 130
LVD 2 Disconnect Voltage: LVD 2 low voltage disconnect setting (when LVD set for voltage) LVD 2 Reconnect Voltage: LVD 2 reconnect setting (when LVD set for voltage). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 131
SMTemp# Temp# Low: Sets temperature port # on the SM-Temp # module “Temperature Low” alarm point. • Clear SM Temp Lost Alarm: Clears an SM Temp lost alarm. The only selection is Clear. Once Clear is selected and confirmed, the alarm clears. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 132
If “Rectifier On at AC Overvoltage" feature is enabled, the rectifier is forced to turn on. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 133
• Clear Rect Comm Fail Alarm: Clears a rectifier communication fail alarm. The only selection is Yes. Once Yes is selected and confirmed, the alarm clears. • Rectifier Upgrade: Not Available. • Normal Update: Not Available. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 134
(12) battery discharge tests per year. • Clear Bad Battery Alarm: Clears a bad battery alarm. The only selection is Yes. Once Yes is selected and confirmed, the alarm clears. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 135
• Get time automatically from the following servers. When selected, the controller will get the time from the selected time server. The controller will also adjust the time per the "Local Zone" setting. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Select Device and Time Select the "Device" to query from the drop-down list box. Select the "from" and "to" time. Figure 38: Alarm History Log Device and Time Selection Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 137
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 40: Alarm History Log Upload Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 138
Select Battery Test Number Select the Battery Test Log to query from the drop-down list box. Battery test #1 is the most recent. Figure 41: Battery Test Log Number Selection Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 139
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 43: Battery Test Log Upload Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 140
Event Log Tab Select Time Select the "from" and "to" time. Figure 44: Event Log Time Selection Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 141
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 46: Event Log Upload Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 142
Select Device and Time Select the "Device" to query from the drop-down list box. Select the "from" and "to" time. Figure 47: Data History Log Device and Time Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 143
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 49: Data History Log Upload Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 144
System Log Tab Select Time Select the "from" and "to" time. Figure 50: System Log Time Selection Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 145
Click “Upload” to open the log into another window. You can then save the log as an .html (Web page) or .txt (text) file. Figure 52: System Log Upload Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
System Inventory Menu The System Inventory Menu allows you to view product information of the intelligent devices (i.e. controller, rectifiers, etc.) connected to the controller. Figure 53: System Inventory Menu Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
After modifying the network parameters, click "Save" to validate the change made to the parameters. NOTE! After changing the IP Address, you will need to login again with the new IP address. Figure 54: Ethernet Tab Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 148
• A maximum of sixteen (16) Users can be set up in the controller. • A maximum of five (5) Users can access the controller at the same time. Figure 55: Users Tab Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 149
To reset the form (i.e. to start over) and erase all information entered, click on the “Reset” button. Deleting a User Select the User to be deleted from those listed in the "User Information" list. Click the "Delete" button to delete this User. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 150
High Load Level 2 (%) Engineer not available Relay Test (type) Engineer not available Relay Test Time (sec) Engineer not available Ambient Temp Sensor (select from list) Engineer not available Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 151
Operator Number of Battery Fuses (0 to 6) Operator not available Calculate Battery Current (yes or no) Engineer not available Temp Comp Sensor (select from list) Engineer Operator Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 152
Cyclic Equalize Start Time (date and Engineer not available time) Charging Efficiency (%) Engineer not available Time to ##C10 Discharge (10 values in Engineer not available Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 153
## Temp# High1 (deg) Engineer not available ## Temp# Low (deg) Engineer not available Settings / Current Limit (enable/disable) Operator Operator Rectifiers Current Limit Point (A) Engineer Operator Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 154
Clear Cycle Alarm (yes) Operator not available Clear Rectifier Lost Alarm (yes) Operator Operator Clear Rect Comm Fail Alarm (yes) Operator Operator Settings / Battery Battery Test Control (stop/start) Operator Operator Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 155
Get Time Automatically from Time Engineer not available Servers Primary Server IP Engineer not available Secondary Server IP Engineer not available Interval to Adjust Time (min) Engineer not available Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 156
NMSV3 Configuration – delete command Administrator not available NMSV3 Configuration – User Name Administrator not available NMSV3 Configuration – Priv Password Administrator not available NMSV3 Configuration – Auth Password Administrator not available Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 157
Settings / Shunts Used/General/load/Battery/Source) Signal Full Name Administrator not available Signal Abbreviated Name Administrator not available Full Scale Current (A) Administrator not available Full Scale Voltage (mV) Administrator not available Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 158
Power Split Mode (enable/disable) Administrator not available Settings / Power LVD# Equipment Administrator not available Split LVD# Signal Type Administrator not available LVD# Signal Name Administrator not available Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 159
Administrator not available Advanced Alarm History Administrator Browser Settings / Clear Data History Administrator not available Data Event Log Administrator not available Battery Test Log Administrator not available Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 160
To reset the form (i.e. to start over) and erase all information entered, click on the “Reset” button. Deleting an Entry Select the Entry to be deleted from those listed at the top of the screen. Click the "Delete" button to delete this Entry. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 161
To reset the form (i.e. to start over) and erase all information entered, click on the “Reset” button. Figure 56: SNMP - NMSV2 Configuration (cont’d on next page) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 162
Figure 56: SNMP - NMSV2 Configuration (cont’d from previous page) IPV6 checkbox appears once you start typing an NMS IP. Check the IPV6 box when entering an IPV6 address. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 163
Controller must be reset after configuration of initial SNMP v3 User (Advanced Settings Menu / SW Maintenance Tab / Restore Factory Defaults / Reboot Controller). Figure 57: SNMP - NMSV3 Configuration Check the IPV6 box when entering an IPV6 trap address. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 164
See Figure 59 to change the language the local display and Web Interface uses. Figure 58: Language Tab Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 165
Click on a language option here that the Web Interface menus will use before entering a User Name and Password. Web Interface Login Screen Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 166
The auto configuration feature scans the system for intelligent equipment connected to controller and configures these into the controller automatically. To start the auto configuration process, click on the "Auto Config" button. Figure 61: Auto Config Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 167
Refer to “Reloading a Backed-Up Controller Configuration” on page 48 to reload the supplied “SettingParam.tar” file. TO RESTORE THESE SYSTEMS TO THE CONTROLLER CONFIGURATION AS SHIPPED, RESTORE DEFAULTS AS DESCRIBED ABOVE; THEN RELOAD THE SUPPLIED "SETTINGPARAM.TAR" FILE. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 168
"SettingParam.tar" files saved. The new name can use alpha and numeric characters preceding the original “SettingParam.tar” name (the end of the new file name must always be “SettingParam.tar”; for example, an acceptable filename would be “seville4SettingParam.tar”). Figure 63: Retrieve "SettingParam.tar" File Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 169
To upload or download a file, you need to shut down the controller first. When you select the SW Maintenance Tab, click on the “Stop Controller” button. Figure 64: Upload/Download - Stop Controller The following window opens. Figure 65: Upload/Download --Controller Stopped Click "OK". Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 170
A Language Package is a package of files containing all the default names of the parameters in two languages. Typically these would be in English and Spanish. The language package cannot be changed by the User. Consult Vertiv if a different language package is required. NOTE! A file named “SettingParam.tar”...
Page 171
Select the equipment type to display the alarms associated to it. Also displayed is the alarm level and alarm relay number assigned to this alarm. To modify the alarm level and/or alarm relay number, click on the “Modify” button for that alarm signal. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 172
The following window opens. Select the New Alarm Level and/or New Relay Number and click on “Set”. “None” means there is no related relay number. Figure 68: Setting Alarm Level / Relay Number Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 173
• Allows you to map the digital input alarms to the alarm relays. • Allows you to set the alarm state for the digital inputs (high or low). Figure 69: DI Alarm Tab Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 174
• New Relay Number: Select a relay number to map to this digital input alarm. “None” means there is no related relay number. • New Alarm State: Select high or low to set the alarm state for the digital input. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 175
To change the relay signal full name (name displayed in the Web Interface menus), click on the “Modify” button for that relay. The following window opens. Figure 72: Changing Relay Signal Full Name Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 176
• Allows you to set the shunts parameters. Figure 73: Shunts Tab Procedure To modify the shunt parameters, click on the “Modify/View” button for that shunt. The following window opens. Figure 74: Setting Shunt Parameters Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 177
• High 2 Curr Alarm Severity: Alarm level for this alarm. (See also Table 1 on page 11.) • High 2 Curr Alarm Relay: Select a relay number to map to this alarm. “None” means there is no related relay number. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 178
Change the following parameters as desired and click on “Set”. • Signal Full Name: Name displayed in the Web Interface menus. • Signal Abbr Name: Name displayed in the local display menus. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 179
SMTP Account: SMTP account number. Obtain from your IT department. SMTP Password: SMTP password. Obtain from your IT department. • Alarm Report Level: Select the level of alarm reports you want to receive. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 180
• Alarm Report Level: If you only want to use the Forgot Password Feature, set the Alarm Report Level to None. SMS Section • In the SMS section, you can set cell phone number for receiving alarm reports and the alarm report level. NOTE! Not Available. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 181
Split Feature” on page 17 and “Power Split Feature” on page 50 for more information on the Power Split feature. Figure 78: Power Split Tab Figure 79: Power Split Settings Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 182
For EQUALIZE_CHARGE, click on the “Modify” button and select the controller digital input connected to the existing systems equalize control circuit. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 183
You can select "EEM", "YDN23", "Modbus" or “TL1” as the protocol. To make the new protocol valid, click the “Valid after Restart" button. Figure 80: Monitor Protocol Tab Figure 81: Valid after Restart Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 184
• CCID: Enter value per site requirements. • Maximum Alarm Report Attempts: Enter value per site requirements. • Call Elapse Time: Enter value per site requirements. • Safety Level: Select per site requirements. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 185
You can set YDN23 protocol parameters. Figure 83: YDN23 Protocol • Protocol Media: Select RS-232, Modem, or IPV4 per site requirements. • Self Address: Enter the parameter per site requirements. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 186
You can set Modbus protocol parameters. Figure 84: Modbus Protocol • Protocol Media: Select RS-232, Modem, or IPV4 per site requirements. • Self Address: Enter the parameter per site requirements. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 187
This is a unique name which identifies the controller in an NMA system. This data parameter is used to identify the destination of command messages and the source of response and autonomous messages in an NMA system. Set per site requirements. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 188
Select the data log to be cleared from those listed in the drop-down list box. Click on the “Clear” button to clear the corresponding data. Figure 86: Clear Data Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 189
The sub-access identifier identifies a specific sub-entity within an NMA system, such as a specific rectifier. Only alpha-numeric characters can be entered for this parameter. TL1 uses specific values for this parameter. Refer to TA-NWT-001360, Table 4-1. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 190
• ENV, refers to environment entities or entities that are external to the NMA system (ex. air conditioners, fans, etc.) Click the submit button. Repeat these steps for the remaining Access Identifiers (AID). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 191
A list of signals associated to this AID Group appear in the left window pane. Select a signal in the AID Group to be configured. The AID to signal associations cannot be changed by the customer. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 192
(binary) values. Only alpha characters can be entered for this parameter. TL1 uses specific values for this parameter. Refer to TA-NWT-001360 Table 6-1. Click the Submit button. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 193
Repeat these steps for other signals to be added to the AID group and to assign signals to other AID groups. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
ENTER. Data is encrypted in the transmission. You can also browse/set the MIB library with SNMP v3. Data is also encrypted in the transmission. SNMP V3 IE Browser MIB Browser Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
MIB Installation Installation The controller’s MIB is named "Netsure-Controller.mib". Contact your Vertiv representative for the location on the Web to download the MIB file. Use the MIB loading function of the NMS to load the MIB database. Refer to the User Manual provided with the NMS for the detailed loading method.
(8) restricted (9) testing (10) disabled systemVoltage System voltage, stored as mV. systemCurrent System current, stored as mA. systemUsedCapacity Used capacity, stored as percentage of the total capacity. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 197
Temperature measurement table entry. psTemperatureIndex Temperature probe number. psTemperatureMeasurement Temperature value in centigrade. psTemperatureName Configured temperature probe name. Temperature Probe Type. (1) none psTemperatureType (2) ambient (3) battery Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 198
The number of SM IO module. Rectifier Group psNumberOfInstalledRectifiers Number of rectifiers. psNumberOfRectifiersCommunic Number of rectifiers communicating. ating psRectifiersUsedCapacity Used capacity, stored as % of the total capacity. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 199
Distribution name. Distribution General Table psDistributionGeneralTable Table of non-load shunts. psDistributionGeneralEntry Distribution measurement table entry. psDistributionGeneralIndex Automatically generated index object. psDistributionGeneralCurrent Distribution current in amps. psDistributionGeneralName Distribution name. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 200
Control relay test, start (1), stop (0). Equipment Signal Table psEquipmentSignalTable Table of indexed equipment signal values. equipmentSignalTableEntry An entry (conceptual row) in the equipment signal table. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 201
(3) major - MA (4) critical - CA, highest level of alarm severity alarmDescription Free-text description of alarm. alarmType Alarm type, i.e. an integer specifying the type of alarm. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 202
Free-text description of alarm. * alarmType Integer indicating type of alarm. In Table 7, R means OID is read-only (GET), and R/W means OID can be read and modified (GET/SET). Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
• Once a valid TL1 port User session is established, valid request messages will be accepted. TL1 Autonomous Messages • Autonomous TL1 messages are outputted through the TL1 port whenever one is pending and there is a valid port connection. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
• If the TL1 port connection is not present, then the data is maintained and outputted when a port connection becomes present. TL1 Port Configuration Refer to “TL1 Protocol” on page 187. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Requests a system RTRV-HDR <null> not used header message. Report of REPT-ALM- alarms as varies EQPT they occur and clear. CANCEL- User timeout <null> not used SESSION message. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 206
<atag> is the autonomously generated ID (like a sequence number) <rspblk> is the detailed information about the alarm; see details below. Verb <response parameter blocks> REPT-ALM-EQPT Alarm details. CANCEL-SESSION <null> Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
The controller responds with this message: Lorain 15-09-25 08:17:55 40 COMPLD "SYSTEM:M830B::SWVER=1.00,CURSWVER=1.1.41T04,:IS-NR," < The controller type is M830B. The configuration is version 1.00. The software version is 1.1.41T04. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 208
Here is an example of the controller response when an invalid command (RTRV-ALM-EQPTX::ALL:57::CR;) is sent: Lorain 15-09-25 08:18:15 57 DENY ICNV /* Command not valid */ < Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Instructs the system to send the current controller software version and the RTRV-EQPT controller software configuration part number and revision. RETRIEVE-HEADER Requests that the system reply with a "normal" response indicating RTRV-HDR COMPLD. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
^^^<source identifier>^<date>^<time> cr lf M^^<ctag>^COMPLD cr lf ^^^/* This is a private computer system. cr lf Unauthorized access may result in criminal prosecution */ cr lf; Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 211
No response is returned if a valid User session has not been established. Otherwise the response is in the following format. cr lf lf ^^^<source identifier>^<date>^<time> cr lf M^^<ctag>^COMPLD cr lf Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 212
This is the effect on service caused by the alarm condition. Valid values for this parameter are as follows: service-affecting condition nonservice-affecting condition <null> request retrieval of alarm conditions for both of the above codes Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 213
This is the notification code associated with a single alarm condition given in this block. <condtype> This is the condition type of the alarm condition being given in this block. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 214
The following parameters will either not be implemented or do not apply to this application. A <null> value is returned for these parameters. <aiddet> - supplementary equipment identification <obsdbhvr> - observed behavior that resulted in reported trouble Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 215
<exptdbhvr> - expected behavior that was deviated from <dgntype> - diagnostic routine used to isolate trouble <tblistl> - provides isolation information Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 216
<null>. <dspswver> Version of DSP code on the device. This parameter does not apply to this application. A value of <null> is always outputted for this parameter. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 217
<sst> This is the secondary state of the equipment. This parameter is not available in this application. A value of <null> is always outputted for this parameter. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 218
RTRV-HDR:[<tid>]:<aid>:<ctag>; <aid> The <aid> in this command must be <null> since it does not apply. Normal Response Format: cr lf lf ^^^<source identifier>^<date>^<time> cr lf M^^<ctag>^COMPLD cr lf Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
^^^<sid>^<YY-MM-DD>^<HH:MM:SS> cr lf A^^<atag>^CANC cr lf <uid> cr lf ; <uid> This is the User whose session is terminated as a result of the timeout. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 220
This is the condition type of the alarm. It indicates the type of failure that has occurred/cleared. <srveff> This is the effect on service caused by the single alarm condition given in this block. Valid values are as follows: Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 221
If the parameter has not been configured, a <null> is inserted for this parameter. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 222
- observed behavior that resulted in reported trouble <exptdbhvr> - expected behavior that was deviated from <dgntype> - diagnostic routine used to isolate trouble <tblistl> - provides isolation information Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
PIUI - Privilege, Illegal User Identity SARB - Status, All Resources Busy SCNF - Status, Command Not Found SDNR - Status, Data Not Ready SROF - Status, Requested Operation Failed Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
If these alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while this procedure is being performed. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 225
Wait for the controller to finish booting and verify that the complete system operates normally. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
227 for ratings. NOTE! Note that some relay outputs may be factory programmed for a specific use. Refer to the controller Configuration Drawing (C-drawing) furnished with your system. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
• Electrical: IEC 60950-1, EN 60950-1, UL 60950-1 • EMC: EN 300 386, 2001 Class B; FCC Part 15, Class B • Environmental: CE; NEBS Level 3 (pending) • GR-3108 Class 2 Compliant (pending) Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 228
• Calibration Error (-25 °C to +105 °C): ±2 °C • Nonlinearity (-25 °C to +105 °C): 0.4 °C Controller Temperature Probe Input Accuracy (-10 °C to +65 °C): ±2 °C Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...
Page 229
This page is intentionally blank. Vertiv | NetSure™ Mini Control Unit User Manual (UM1M831ANA) | Rev. B...