Table 6. MBM/PDM Terminal Block (TB10) Wiring
Wire
Function
Input
Output
* Use only 75°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long
service runs. Follow local requirements.
3 3 . . 4 4
I I n n s s p p e e c c t t i i n n g g a a n n d d U U n n p p a a c c k k i i n n g g t t h h e e E E q q u u i i p p m m e e n n t t
The cabinet is shipped bolted to a metal and wood pallet with outer protective packaging material covering the
cabinets.
1.
Carefully inspect the outer packaging for evidence of damage during transit.
Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative
immediately.
NOTE
2.
Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible,
before unpacking. If possible, move the cabinet using the pallet. Insert the forklift or pallet jack forks
between the supports on the bottom of the pallet.
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for
removing the cabinet from the pallet.
4.
Remove the protective packaging material from the cabinet and recycle in a responsible manner. Retain
any parts kits packaged with the cabinet.
5.
Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact an Eaton service representative immediately to
determine the extent of the damage and its impact on further installation.
If any equipment has been damaged during shipment, keep the shipping and packing materials for the
carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance,
file a claim for concealed damage.
Input Circuit
Breaker Rating
Ground
L1
8 kVa
60A
Neu-
10 kVA
80A
tral
12 kVA
100A
15 kVA
100A
L2
L1
Neu-
tral
L2
Ground
Check the battery recharge date on the packaging label. If the date has expired and the
batteries were never recharged, do not use the UPS. Contact your service
representative.
Minimum
Wire Size*
8 AWG
4 AWG (21.2 mm
2
)
3 AWG (26.7 mm
2
)
2 AWG (33.6 mm
2
)
2 AWG (33.6 mm
2
)
3 AWG
3 AWG
3 AWG
8 AWG
CAUTION
Eaton 9155 Parallel UPS (8–15 kVA) User's Guide 164201592—Rev E0
UPS Installation Plan and Unpacking
Tightening
Conduit
Torque
Connection
(Entry Size)
120 lb in
2" access hole for
(13.5 Nm)
1-1/2" conduit
120 lb in
2" access hole for
(13.5 Nm)
1-1/2" conduit
13