YASKAWA FSDrive-MV1S Instructions Manual page 88

Super energy-saving medium-voltage inverter
Table of Contents

Advertisement

Name
Constant
Number
Display
Motor rated output
E2-11
Mtr Rated Power
Motor wiring resistor
E2-12
Wiring Resistor
Motor temperature OH
level
E2-13
Motor Temp OHLVL
Motor Thermistor
selection
E2-14
Motor Thermistor
* 1. The factory settings depend on the Inverter capacity.
* 2. Only multiples of 2 can be set.
Setting
Description
Range
Set the rated output of the
motor in units of 0.01 kW.
This constant is automatically
10000
set during autotuning.
Set the motor wiring resistance
0.00 to
in % units.
Set the motor temperature OH
50 to
level in °C units.
0: Motor Thermistor disabled.
0 or 1
1: Motor Thermistor enabled.
User Constant Tables
Change
Factory
during
Open-
Setting
Operation
loop
Vector
0 to
630
No
Q
kW
0.00%
Yes
A
1.00
120°C
No
A
200
0
No
A
Control
Methods
MEMOBUS
Register
Flux
Vector
Q
36AH
A
36BH
A
36CH
A
36DH
23
5-