If The Motor Does Not Operate - YASKAWA FSDrive-MV1S Instructions Manual

Super energy-saving medium-voltage inverter
Table of Contents

Advertisement

If the Motor Does Not Operate

Use the following information if the motor does not operate.
The motor does not operate when the RUN Key on the Digital Operator is pressed.
The following causes are possible.
IMPORTANT
The operation method setting is wrong.
If constant b1-02 (Operation Method Selection) is set to any number but 0 (control circuit terminal), the motor
will not operate when the Run Key is pressed. Either press the LOCAL/REMOTE Key to switch to Digital
Operator operation or set b1-02 to 0 (Digital Operator).
INFO
The frequency reference is too low.
If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the Inverter
will not operate.
Raise the frequency reference to at least the minimum output frequency.
There is a multi-function analog input setting error.
If multi-function analog input H3-05, H3-09 or H3-13 is set to 1 (frequency gain), and if no voltage (current)
is input, then the frequency reference will be zero. Check to be sure that the set value and analog input value
are correct.
The motor does not operate when an external operation signal is input.
The following causes are possible.
The Inverter is not in drive mode.
If the Inverter is not in drive mode and the DRIVE indicator does not light up, the Inverter will remain in
ready status and will not start. Press the MENU Key to make the DRIVE indicator flash, and enter the drive
mode by pressing the DATA/ENTER Key. "-Rdy-" will be displayed when drive mode is entered.
-12
7
If the Inverter is not in drive mode and the DRIVE indicator on the Digital Operator (JVOP-160) does not light
up, the Inverter will remain in ready status and will not start. Press the Menu Key to display the drive mode,
and enter the drive mode by pressing the DATA/ENTER Key. "-Rdy-" will be displayed when drive mode is
entered.
The LOCAL/REMOTE Key is enabled by setting o2-01 to 1 and disabled by setting o2-01 to 0. It is enabled
when the drive mode is entered.

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents