1. The external connection terminals include main circuit input terminals (R, S, and T), main circuit output ter-
minals (U, V, and W), a grounding terminal (EA), and control circuit terminals. The control circuit terminals
include control power supply input terminals (RC, SC, and TC), analog I/O terminals (L1 to L15), and
sequence I/O output terminals (1 to 40).
IMPORTANT
2. The analog I/O terminals (frequency reference input) are for 4 to 20 mA of current input.
3. The analog output terminals are for monitoring output frequency and current. They are not used for con-
trols such as feedback control. Be careful not to short a circuit between terminals. Doing so will cause mal-
function or fault of Inverter.
4. The sequence input terminals 1 through 12 are labelled for sequence connections for no-voltage contacts.
The sequence output terminals are for relay output. Refer to Table 2.5 for the sequence I/O terminal speci-
fications.
5. Do not use terminals other than grounding terminals for grounding. Doing so may cause malfunction or
fault.
6. For flux vector control, PG circuit wiring is required in addition to the standard wiring. Contact your
Yaskawa representative if wirings other than the standard wiring are required.
Standard Wiring