Stopping Methods

This section explains methods of stopping the Inverter.

Selecting the Stopping Method when a Stop Command is Sent

There are two methods of stopping the Inverter when a Stop Command is sent:
Deceleration to stop
Coast to stop
Set constant b1-03 to select the Inverter stopping method.
Related Constants
Name
Constant
Number
Display
Stopping method
selection
b1-03
Stopping Method
Operation selection for
setting E1-09 or less
b1-05
Zero-Speed Oper
Zero-speed level (DC
injection braking
starting frequency)
b2-01
DCInj Start Freq
DC injection braking
current
b2-02
DCInj Current
DC injection braking
time at start
b2-03
DCInj Time@Start
DC injection braking
time at stop
b2-04
DCInj Time@Stop
* The factory setting will change when the control method is changed.
Setting
Description
Range
Used to set the stopping
method used when a Stop Com-
mand is input.
0 or 1
0: Deceleration to stop
1: Coast to stop
Used to set the method of
operation when the frequency
reference input is less than the
minimum output frequency
(E1-09).
0: Run at frequency reference
(E1-09 not effective).
0 to 3
1: STOP (Frequencies below
E1-09 in the coast to stop
state.)
2: Run at min. frequency.
(E1-09)
3: Run at zero-speed (Frequen-
cies below E1-09 are zero)
Used to set the frequency
which starts DC injection brak-
ing in 1% units when decelera-
0.00 to
tion to stop is selected.
10.00
When b2-01 is less than E1-09,
E1-09 becomes the DC injec-
tion braking starting frequency.
Sets the DC injection braking
current as a percentage of the
Inverter rated current.
Used to set the time to perform
DC injection braking at start in
units of 1 second.
Used to stop coasting motor
and restart it. When the set
10.00
value is 0, DC injection braking
at start is not performed.
Used to set the time to perform
DC injection braking at stop in
units of 1 second.
Used to prevent coasting after
the Stop Command is input.
10.00
When the set value is 0.00, DC
injection braking at stop is not
performed.
Change
Factory
during
Open-
Setting
Operation
loop
Vector
1
No
Q
1*
No
No
0.50%
No
A
*
0 to
50%
No
A
100
0.00
0.00
to
No
A
s
0.00
0.50
to
No
A
s

Stopping Methods

Control
Methods
MEMOBUS
Register
Flux
Vector
Q
1A2H
A
1A4H
A
1B0H
No
1B1H
A
1B2H
A
1B3H
6-
5