7.3 Setting up the IP addresses

The CIM 500 ethernet module is default set to a fixed IP address.
It is possible to change the IP address settings from the built-in
webserver.
Default IP settings
IP address:
used by the
Subnet mask: 255.255.255.0
webserver
Gateway:
IP settings for
Configure the settings via the webserver.
Modbus TCP

7.4 Establish connection to the webserver

You can configure the CIM 500 module using the built-in
webserver. To establish a connection from a PC to CIM 500, the
following steps are required:
Connect the PC and the CIM 500 module using an ethernet
cable
Configure the PC ethernet port to the same subnetwork as
CIM 500, for example 192.168.1.101, and the subnet mask to
255.255.255.0. See section
on page 57.
address on your PC
Open a standard Internet browser and type 192.168.1.100 in
the URL field.
Log in to the webserver using the following:
User name
Password
User name and password may have been changed
from their default values.
Fig. 17 CIM 500 connected to PC via ethernet cable
For further information on how to use the webserver, see section
on page 58.
A.2 Webserver configuration
You can use both ETH1 and ETH2 to establish a
connection to the webserver.
You can access the webserver while the selected
Industrial protocole is active.
14
192.168.1.100
192.168.1.1
A.1 How to configure an IP
admin (default)
Grundfos (default)

7.5 Status LEDs

The CIM 500 ethernet module has two Status LEDs: LED1 and
LED2. See fig. 15.
Red and green status LED1 for ethernet communication
Red and green status LED2 for internal communication
between CIM 500 and the Grundfos product.
LED1
Status
Description
No Modbus TCP communication or
Off
switched off.
Flashing green
Modbus TCP communication active.
CIM 500 module configuration fault. See
Permanently red
section
Permanently red and
Error in the firmware download. See
green
section
Flashing red and
Resetting to factory default.
green
After 20 seconds, CIM 500 restarts.
LED2
Status
Description
Off
CIM 500 is switched off.
No internal communication between CIM
Flashing red
500 and the CIU 502 unit.
CIM 500 does not support the Grundfos
Permanently red
product connected.
Internal communication between CIM
Permanently green
500 and CIU 502 is OK.
Permanently red and
Memory fault.
green
During startup, there is a delay of up to 5 seconds
before LED1 and LED2 status is updated.

7.6 DATA and LINK LEDs

The CIM 500 ethernet module has two connectivity LEDs related
to each RJ45 connector. See fig. 15.
DATA1 and DATA2
These yellow LEDs indicate data traffic activity.
Status
Description
Yellow off
No data communication on the RJ45 connector.
Yellow
Data communication ongoing on the RJ45
flashing
connector.
Permanently
Heavy network traffic on the RJ45 connector.
yellow
LINK1 and LINK2
These green LEDs shows whether the ethernet cable is properly
connected.
Status
Description
Green off
No ethernet Link on the RJ45 connector.
Green on
Ethernet Link on the RJ45 connector is OK.
14.3.1 LED