13.11 Reset alarm

This section shows how to reset an alarm. In the example, slave
address 0x01 (1) is used. The ResetAlarm is the first bit in
register 00101, so the bit must be set from 0 to 1.
Request from master to slave
Field
Value
Slave address
0x01
Function code
0x06
Start address HI
0x00
Start address LO
0x64
Value HI
0x00
Value LO
0x01
Example of response from slave to master
Field
Value
Slave address
0x01
Function code
0x06
Start address HI
0x00
Start address LO
0x64
Value HI
0x00
Value LO
0x01
If there is no response from the slave, see section
finding.
46
Description
-
Write single register
ControlRegister address:
00101 (0x0065)
-
Set the value to 1.
-
Description
-
Write single register
ControlRegister address:
00101 (0x0065)
-
Set the value to 1.
-