Address
Register name
00115
SetMultiPitPump3StartLevelMax
00116
SetMultiPitPump3StartLevelBand
00117
SetMultiPitPump3HighWaterLevel 0.01 m
00118
SetMultiPitPump4StopLevel
00119
SetMultiPitPump4StartLevelMax
00120
SetMultiPitPump4StartLevelBand
00121
SetMultiPitPump4HighWaterLevel 0.01 m
00122
PitPump1Control
00123
PitPump2Control
00124
PitPump3Control
00125
PitPump4Control
22
Scale
Description
Setting of start level max., pump 3. Used in multi-pit mode only.
0.01 m
Pit mode: 1. Pit mode is set in register 00203.
Setting of start level band, pump 3. Used in multi-pit mode only.
0.01 m
Pit mode: 1. Pit mode is set in register 00203.
Setting of high water level, pump 3. Used in multi-pit mode only.
Pit mode. 1. Pit mode is set in register 00203.
Setting of stop level, pump 4. Used in multi-pit mode only.
0.01 m
Pit mode: 1. Pit mode is set in register 00203.
Setting of start level max., pump 4. Used in multi-pit mode only.
0.01 m
Pit mode: 1. Pit mode is set in register 00203.
Setting of start level band, pump 4. Used in multi-pit mode only.
0.01 m
Pit mode: 1. Pit mode is set in register 00203.
Setting of high water level, pump 4. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
Remote manual control of pump 1.
0: "Auto" mode
Enum
1: Forced start
2: Forced stop.
Remote manual control of pump 2.
0: "Auto" mode
Enum
1: Forced start
2: Forced stop.
Remote manual control of pump 3.
0: "Auto" mode
Enum
1: Forced start
2: Forced stop.
Remote manual control of pump 4.
0: "Auto" mode
Enum
1: Forced start
2: Forced stop.